„ ELECTRICAL WIRING
z Electricity meter connection composition
To perform energy saving peak cut control, electricity meters with pulse transmission function
measuring all the power consumed by the air conditioner are necessary. Multiple meter
installations are also possible as long as the number of electricity meters is within the specified
limit. A general electricity meter installation configuration is shown below.
Electricity meter
Pulse constant
reference point
VT
(PT)
Pulse unit
VT
reference point
(PT)
Pulse constant
reference
point
Electricity meter
Item
Electricity meter
Measures the voltage and current of the power cable to which measurement
line is connected and finds the Input Power from these. In addition, pulses
corresponding to the measured value are output to the transmission line.
VT(PT)
Voltage Transformer (Power Transformer)
Transform the power source voltage to a measurable voltage. Transformation
ratio is indicated by VT (PT) ratio.
Normally unnecessary for the voltage value level used by outdoor units and
indoor units.
CT
Current Transformer
Transform the power line current value to a current measurable by an
electricity meter. Transformation ratio is indicated by CT ratio.
Some meters are connected inline with the power lines and some are clamped
on the power lines.
Pulse unit
Pulse unit indicates the relationship between electricity meter output pulse and
measured power. The value specified in pulse unit indicates the power in kWh
consumed on the power cable for 1 pulse.
Units: [kWh/pulse]
The value specified by pulse unit takes into account the VT and CT ratio used
and corresponds to the actual Input Power itself.
Pulse unit reference
Indicates the measurement point of the Input Power specified in pulse units.
point
Pulse constant
Pulse constant indicates the relationship between electricity meter measured
power and output pulses. The value specified by pulse constant indicates
how many pulses are equivalent to 1kWh of Input Input Power to an electricity
meter.
Units: [pulse/kWh]
Because the ratio of VT and CT used is not taken into account in the value
specified by pulse constant, to find the actual Input Power on the power cable,
the pulse constant value must be multiplied by both the VT and CT ratio.
Pulse constant
Indicates the measurement point of Input Power specified by pulse constant.
reference point
pulse
transmission
line
to CN135
measurement
line
Outdoor unit
CT
Power cable
Indoor unit
measurement
line
RB unit
Transmission line (VRF Network)
Description
- (07 - 155) -
System Controller
Internet
System Controller
(Remote site)
Locally purchsed parts
▪Electricity meter
Touch panel
controller
▪CT
▪VT (PT)
pulse transmission line