Fujitsu Airstage J-II Series Design & Technical Manual page 723

Small vrf system
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Change of unit
2
8
(Temperature)
Change of unit
2
9
(Pressure)
Outdoor unit
3
0
capacity save
setting
3
1
Prohibited
3
4
Prohibited
Presence of
heater selection
3
5
control using
outdoor
temperature
Outdoor
temperature
zone boundary
3
6
temperature
A
*1: Do not set this for outdoor units with Slave setting.
LED104
Setting Function
CODE No.
0
0
Celsius (°C)
0
1
Fahrenheit (°F)
0
0
MPa
0
1
psi
0
0
Level 1 (stop)
0
1
Level 2
0
2
Level 3
0
3
Level 4
0
4
Level 5
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Disable
0
1
Enable
0
0
-4.0°F (-20°C)
0
1
-0.4°F (-18°C)
0
2
3.2°F (-16°C)
0
3
6.8°F (-14°C)
0
4
10.4°F (-12°C)
0
5
14.0°F (-10°C)
0
6
17.6°F (-8°C)
0
7
21.2°F (-6°C)
0
8
24.8°F (-4°C)
- (07 - 76) -
Factory
Remarks
setting
l
l
l
The capacity limit can be selected by the
external input terminal (CN133) when operating
with the "Outdoor unit capacity save function."
The lower the level, the more the effect
of energy saving, but the cooling/heating
performance will also drop.
l
Setting prohibited
l
Setting prohibited
Setting required to validate the setting of heater
selection control using outdoor temperature 1
l
and 2 (setting value: 03 or 04) in field setting 61
(indoor unit) for heater control switching.
For details, refer to Chapter 8. 1-2-2.
EXTERNAL OUTPUT.
l
Setting required if changing of the outdoor
temperature setting for heat pump prohibition
zone is required when heater selection
control using outdoor temperature 1 and 2 are
performed on the indoor unit.
For details, refer to Chapter 8. 1-2-2.
EXTERNAL OUTPUT.