Fujitsu Airstage J-II Series Design & Technical Manual page 530

Small vrf system
Table of Contents

Advertisement

®
„ BACnet
OBJECT LIST
z Type : Indoor
Object
Code (II)
name
10
Set temp. status
11
Space temp.
12
Auto temp. (Low limit status)
13
Auto temp. (High limit status)
AI
14
Cool/Dry temp. (Low limit status)
15
Cool/Dry temp. (High limit status)
16
Heat temp. (Low limit status)
17
Heat temp. (High limit status)
10
Temp. setting
11
Auto temp. (Low limit setting)
12
Auto temp. (High limit setting s)
13
Cool/Dry temp. (Low limit setting )
AO
14
Cool/Dry temp. (High limit setting )
15
Heat temp. (Low limit setting )
16
Heat temp. (High limit setting )
1
10
ECA *
AV
10
Operation status
14
Filter sign status
15
Indoor unit error status
16
Antifreeze operation status
17
SAVE operation status
BI
18
Forced thermostat off status
19
Emergency stop status
20
Mode mismatch status
21
Protect antifreeze status
22
Temp. limit enable status
10
Operation setting
14
Filter sign resetting
15
Antifreeze operation setting
16
SAVE operation setting
BO
17
Forced thermostat OFF setting
18
Emergency stop setting
19
Temp. limit enable setting
10
Operation mode status
11
Fan speed status
12
Indoor unit error code
13
R.C. prohibition status
MI
14
Vertical airflow direction status
15
Horizontal airflow direction status
16
Special driving status
17
Managed mode
10
Operation mode setting
11
Fan speed setting
12
R.C. prohibition setting
MO
13
Vertical airflow direction setting
14
Horizontal airflow direction setting
1
10
ECA *
TL
1
*
) ECA: Electricity Charge Apportionment
Function
operation data
operation data log
- (05 - 167) -
Inactive
Active
Text-1
Text-2
Text-3
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
OFF
ON
Unsigned Signed
Normal
Fault
Reset
Set
Normal
SAVE
Reset
Set
Normal
Stop
Normal
Mismatch
Reset
Set
Disable
Enable
OFF
ON
Reset
Not reset
Reset
Set
Reset
Set
Reset
Set
Reset
Set
Disable
Enable
Cool
Heat
Fan
Low
High
Med
Refer to FGL original error code
Refer to R.C. prohibition setting chart
1
2
3
1
2
3
Normal
Defrost
Oil
Recovery
None
Master
Slave
Cool
Heat
Fan
Low
High
Med
Refer to R.C. prohibition setting chart
1
2
3
1
2
3
Unit
Text-4
Text-5
Text-6
Dry
Auto
Auto
4
Swing
4
5
Swing
Outer
Dry
Auto
Auto
4
Swing
4
5
Swing