DIL switches
Flow characteristic
SAX61.03 / SAV61.00
with VVF..
Flow characteristic
SAY61P03 / SAX61P03 /
SAV61P00 with VPF..
Note
56 / 87
Siemens
Smart Infrastructure
4.4
Positioning signal and flow characteristic
selection
Positioning signal "Y"
1)
OFF
DC 0...10 V
ON
DC 4...20 mA
1)
Factory setting: All DIL switches set to OFF Ω
Actuator
log
lin
Actuator
log
lin
Y, Z
Positioning signal
H
Stroke
V
Volumetric flow
Acting direction: Direct
Acting direction: Reverse
SAX61.03/MO: Positioning signal and flow characteristic selection are not
permissible
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
Position
feedback "U"
DC 0...10 V
DC 0...10 V
Valve VVF.. / VVG41..
Combi-Valve VPF43/VPF53
Flow characteristic
log =
equal-
percentage
lin =
linear
Totally
Totally
CE1P4040en