15. Notes about source protection:
as if you were supplying a three phase transformer, to allow for
b.
Source protection for the AC input should be treated as if you were
supplying a 150 kVA three phase transformer, to allow for fitter inrush
current.
C. Source protection for the input to the bypass section should be treated
as if you were supplying a 150 kVA three phase transformer, to allow for
transformer magnetization inNsh current.
d.
The input breaker (CM) has a trip rating of 150 Amps AT and an Amp
interrupting capabiiii (AIC) of 25,ooO in symmetrical RMS Amps. See
Table Cl:
Table Q. Equhralent lhnsformer Size for Determining Inrush
Standard Input (Auto Transformer)
16.
The input and bypass three phase feeds should be symmetrical about ground.
due to the existence of voftage surge protection devices.
17. The line-to-line unbalanced output capability of the UPS is limited only by the full
load per phase current values for AC output to critfcaf load shown in Table L on
page A-2. The recommended lineto-line load unbalance is SC% or less.
Installation Manual
EPO
Table P. Remote
TB2
1
2
TWISTED
WIRES (2)
and
not tied into any other circutts.