Siemens SINUMERIK 840D sl Function Manual page 420

Sinumerik safety integrated
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

Diagnostics
10.2 NCK safety alarms for Sinumerik 840D sl
Explanation
Response
Remedy
Program
continuation
27093
Parameter
Explanation
Response
Remedy
Program
continuation
27094
Parameter
Explanation
Response
10-420
SINUMERIK 840D sl/SINAMICS S120 SINUMERIK Safety Integrated (FBSI sl) – 03.2006 Edition
The delay stage (1 s) for the communication monitoring has been
exceeded in the monitoring channel specified in %1 (NCK or PLC). The
other monitoring channel did not send new data within this time.
Alarm display
A STOP D/E is initiated (this can be set using MD
$MN_SPL_STOP_MODE) on all of the axes with safety functionality if
the SPL commissioning phase (MD
$MN_PREVENT_SYNACT_LOCK[0,1] not equal to 0) has been
completed.
A timer of 5 s is started – after it has expired
– The external NCK-SPL outputs are deleted (cleared)
– the PLC goes to stop.
Do not start the SPL anymore. Check the system components (PLC
must have the correct version of FB15 and have DB18).
Power-down the control and power-up again
Checksum error NCK-SPL, %1, %2, %3
%1 = supplementary information about the type of error
%2 = supplementary information about the reference size
%3 = supplementary information about the current size
The checksum error in the NCK SPL. The file
/_N_CST_DIR/_N_SAFE_SPF was subsequently modified.
The safe programmable logic (SPL) in the NCK may be corrupted.
Parameter %1 provides further information about the type of change:
%1 = FILE_LENGTH: The file length has changed.
%1 = FILE_CONTENT: The file contents have changed.
%2 specifies the variable calculated as the reference (file length,
checksum over file contents),
%3 specifies the current size calculated cyclically.
Alarm display
Check the file and when the file was last changed. Reload the original
file and start the monitoring system again with a power on.
Power-down the control and power-up again
Write access to system variable %1 only allowed from NCK-SPL
%1 = name of the safety system variable involved
It is only possible to write access one of the safety system variables
from the part program /_N_CST_DIR/_N_SAFE_SPF. If this error
occurs, an instruction from another part program was detected.
Alarm display
© Siemens AG, 2006. All rights reserved
03.06