Specifi cations
Following are specifi cations for the DeviceNet adapters.
DeviceNet Adapters - PSSCDM12A, PSSCDM18PA
Expansion I/O Capacity
DeviceNet Communication Rate
DeviceNet Power Specifi cations
Power Supply
Input Voltage Rating
DeviceNet Input Voltage Range
Input Overvoltage Protection
DeviceNet Power Requirements
Power Supply Specifi cations
Power Supply
Input Voltage Rating
Input Overvoltage Protection
Inrush Current
PointBus Output Current
Field Side Power Requirements, Maximum
Interruption
General Specifi cations
LED Indicators
• DeviceNet adapter backplane current output = 1.0A maximum.
See the list below for backplane current consumption for each I/O catalog number and
the current consumption for each of the modules connected to the DeviceNet adapter.
Verify that it is below 1.0A.
• Backplane current can be extended beyond 1.0A with a PSSSE24A Backplane
Extension Power Supply. The PSSSE24A can supply up to an additional 1.3A of
backplane current.
• Multiple PSSSE24A modules can be used to reach the
maximum of 63 modules.
Cat. No.
PSSN8xxx
PSSP8xxx
PSST8xxx
PSSTR4M12A
PSSNACM12A
PSSNAVM12A
PSSTACM12A
PSSTAVM12A
PSSS23A
PSSV32A
125K bit/s (500m maximum)
250K bit/s (250m maximum)
500K bit/s (100m maximum)
Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a
NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV)
power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak
or 60VDC under normal conditions and under single fault conditions. A PELV supply has
the same rating and is connected to protected earth.
24VDC nominal
11-25VDC DeviceNet specifi cation
Reverse polarity protected
24VDC (+4% = 25VDC) @ 30 mA maximum
Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a
NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV)
power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak
or 60VDC under normal conditions and under single fault conditions. A PELV supply has
the same rating and is connected to protected earth.
24VDC
10-28.8VDC range
Reverse polarity protected
6A maximum for 10ms
1A maximum @ 5VDC +5% (4.75-5.25)
24VDC (+20% = 28.8VDC) @ 400 mA
Output voltage will stay within specifi cations when input drops out for
10ms at 10V with maximum load
1 green/red Adapter status
1 green/red DeviceNet status
1 green/red PointBus status
1 green System Power (PointBus 5V power)
1 green Adapter Power (24V from fi eld supply)
PointBus Current Requirements
75 mA
75 mA
75 mA
90 mA
75 mA
75 mA
75 mA
75 mA
75 mA
75 mA