Make Cable Connections
Install Open-Style
Connectors
Publication DNET-UM072C-EN-P - July 2004
To attach a plug-in open-style connector to a round media (thick or thin) trunk
line:
1. Strip 65 mm (2.6 in.) to 75 mm (2.96 in.) of the outer jacket from the
end of the cable, leaving no more than 6.4 mm (0.25 in.) of the braided
shield exposed.
jacket
braided shield
2. Wrap the end of the cable with 38 mm (1.5 in.) of shrink wrap, covering
part of the exposed conductors and part of the trunk line insulation.
jacket
3. Strip 8.1 mm (0.32 in.) of the insulation from the end of each of the
insulated conductors.
jacket
4. Tin the last 6.5 mm (0.26 in.) of the bare conductors so that the outside
dimension does not exceed 0.17 mm (0.045 in.).
5. Insert each conductor into the appropriate clamping cavity of the
open-style connector or the screw terminal on the device, according to
the color of the cable insulation.
6.4 mm
(0.25 in.)
65 mm (2.6 in.)
38 mm
(1.5 in.)
shrink wrap
shrink wrap
8.1 mm
(0.32 in.)
41840
41841
41842