Connect To The Trunk Line - Parker H Series Installation & Service Instructions Manual

Fieldbus system
Table of Contents

Advertisement

Class 2 (CL2) KwikLink General
Purpose Cable
Spool Size
Catalog Number
75 m (246 ft)
1485C-P1K75
200 m (656 ft)
1485C-P1K200
420 m (1378 ft)
1485C-P1K420
Class 1 (CL1) KwikLink Power Cable
Spool Size
Catalog Number
75 m (246 ft)
1485C-P1L75
200 m (656 ft)
1485C-P1L200
420 m (1378 ft)
1485C-P1L420

Connect to the Trunk Line

Class 2 (CL2) General Purpose Cable: Well-suited for less-demanding
applications than heavy-duty cable, this design features a micro-style connector
(catalog number 1485P-K1E4-R5) optimized for use with this pliable cable.
1485-P1Kxxx cable cannot be used with KwikLink
IMPORTANT
heavy-duty connectors.
KwikLink Power Cable (CL1): Used to run an auxiliary bus to power
outputs, i.e. valves, actuators, indicators. KwikLink power cable is a Class 1
cable capable of supplying 24V of output power with currents up to 8A.
The ArmorBlock MaXum cable base, 1792D-CBFM, is
TIP
designed to use both the KwikLink network and Auxiliary
Power cables. Use this cable base with all ArmorBlock
MaXum output modules.
The cable system design allows you to replace a device without disturbing the
cable system's operation.
You must terminate the trunk line on each end with a 121
IMPORTANT
Ω, 1%, 1/4W or larger resistor.
Identify Cable System Components
Publication DNET-UM072C-EN-P - July 2004
2-5