Use Terminating Resistors; Ground The Network; Diagnose Power Supply Problems - Parker H Series Installation & Service Instructions Manual

Fieldbus system
Table of Contents

Advertisement

Use Terminating Resistors

Ground the Network

Diagnose Power Supply
Problems
The DeviceNet network may operate unpredictably without terminating
resistors installed at each end of the trunk cable. You can order terminating
resistors, part number 1485A-C2, from your local Rockwell Automation
distributor.
To install terminating resistors:
1. Attach a 121Ω, 1%, 1/4W or larger terminating resistor at each end of
the trunk cable, across the blue (CAN_H) and white (CAN_L) wires of
the cable.
2. Verify resistor connection.
a. Disconnect DeviceNet power.
b. Measure the resistance across the blue (CAN_H) and white
(CAN_L) wires of the cable. Resistance should equal approximately
50 - 60Ω. Resistance will approach 50Ω as more devices are
connected to the network.
You must ground the DeviceNet cable at only one location, closest to the
center of the network.
To ground the network:
1. Using an 8 AWG (10mm
length, connect the following:
a. Connect the network shield and drain wires to an earth ground.
b. Connect the V- conductor (black wire) of the trunk cable to an earth
ground.
c. Connect the DC ground of the power supply to an earth ground.
The DeviceNet network requires 24V dc power. Ensure that the power supply
you are using meets the following requirements.
The DeviceNet power supply must:
• be sized correctly to provide each device with its required power
• be rated 24V dc (+/- 1%)
• have its own current limit protection
• have a rise time of less than 250mS to within 5% of its rated output
voltage
Correct and Prevent Network Problems
2
) wire up to a maximum of 3m (10 ft.) in
Publication DNET-UM072C-EN-P - July 2004
5-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents