3-4
Make Cable Connections
signal conductors
Rear View
Install DeviceBox and
PowerTap Taps
Publication DNET-UM072C-EN-P - July 2004
7. Attach wires to the connector using screw terminals as seen in the
following diagram.
TIP
male connector
power conductors
black
red
white
bare
bare
blue
8. Screw the enclosure body to the connector.
9. Screw the rear nut into the connector enclosure.
IMPORTANT
Cable preparation and attachment is the same for PowerTap taps and
DeviceBox taps which use hard-wire connections of round media. To install
your taps, perform the following steps and then proceed to the appropriate
section for wiring the specific tap.
1. Remove the cover from the tap.
2. Prepare the ends of the cable sections.
a. Strip 65 mm (2.6 in.) to 76 mm (3 in.) of the outer jacket
and braided shield from the end of the cable.
b. Leave no more than 6.4 mm (0.25 in.) of the braided shield exposed.
The following illustration shows a mini male and female
connector. Connections are similar for micro connectors.
female connector
power conductors
signal condctors
Rear View
Do not twist or pull the cable while tightening the rear nut.
76 mm
(3 in.)
jacket
braided shield
black
red
white
blue
bare
bare
41848
41843
6.4 mm
(0.25 in.)
41844