ADT FOCUS 200 PLUS Installation And Setup Manual page 83

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

Entry
Description
Number
26 (TSC)
BA Bell and
Vault Sensor
Test
33 (STC)
System
Trouble
34 (PLC)
Point Link
37 (ACC)
BA Access
38 (HST)
Horn/Strobe
(SIM
Gateway
only)
59 (ACD)
Access
Denied
Function
Output turns on for 30 seconds when a test of the local bell and/or
vault sensors is commanded from the operating panel. When used in
conjunction with the testing of vault sensors, the output can be used
to turn on the test signal transmitter of a vault vibration sensor
system, and/or turn on the test sounder of a vault audio system.
Output turns on for any of the following conditions and remains on
until the condition is cleared:
A point has been installed, but the point has not been properly
entered into the control unit database.
A "comm fail" occurs for a point, an operating panel, or a printer
interface unit.
A tamper condition occurs at a Holdup-type point, a keyswitch
interface, a Remote Bell-type point, an Ambush Start-or End-
type point, or a Remote Power Supply-type point.
A trouble condition occurs at a Janitor Keyswitch-type point.
Output will follow the status of a designated input point, or the
output of a designated Point Link output point.
Output turns on for 10 seconds when:
A valid ID code is entered at the operating panel during the Day
Set condition of the associated BA group.
The BA group is turned to Day Set. A typical application is
having the output control a door-strike release mechanism,
permitting access to a controlled area.
For use with a horn/strobe that will operate for an FA alarm and,
optionally, also for a BA alarm, as follows:
For an FA alarm, strobe will flash continuously and horn will
operate for an ongoing series of five 1-second rings followed by a
5-second pause. Horn/strobe can be silenced only after all FA
points become normal by entering any valid ID code (or
2,2,2,2,2,2); otherwise, turn-off will occur when 10-minute
timeout expires.
For a BA alarm, horn will sound continuously unless silenced by
entering a valid ID code (or automatic turn-off occurs for the BA
group that is involved). Strobe will not operate for a BA alarm.
Note: Set option 3 for NFPA temporal pattern (Yes) for this output
point type.
This output point can be used to trigger a camera or activate an
annunciation device in the event that someone uses a card/key
having a code that either:
Is not in the system.
Does not have Irregular Open, Open, or Close access to all BA
groups associated with that ACIU.
Does not have the Irregular Open or Open option for any of the
associated BA groups that may be On.
Has a Close option and the person attempts to enter outside of
the scheduled Open period even though the associated protection
is Off.
When the point is triggered, the output will stay on for 10 seconds
and then go off.
Section 9 – J5 Output Triggers
9-3