ADT FOCUS 200 PLUS Installation And Setup Manual page 200

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
471943 Housing Unit
The 471943 Housing Unit is used to house one SIM gateway, one Micro PID, or one relay module.
Consists of a white plastic box with hinged cover (3-1/2" L x 3-l/2" W x 1-5/8" D).
472352 Housing Unit
The 472352 Housing Unit is used to house two SIM ateways, one PID gateway, two Micro PIDS, one
Quad PID, two COPIDS, two keyswitch interfaces, or a printer interface unit. Consists of a white
plastic box with hinged cover (9-1/4" L x 5" W x 1-5/8" D) (23.5cm x 12.78cm x 4.1cm).
248026 Assembly SPDT Relay Module
248309 SIM Relay Module Kit
494465 Quad Trunk Cable (B6465)
Four-conductor trunk cable (off white/sheathed, formerly blue) that is used for the RS-485 bus to
connect gateways, operating panels, and printer interface. It is also used for the gateway trunk.
Suitable for BA and FA applications. Consists of two #19 AWG and two #16 AWG solid conductors;
colors are black, red, yellow, and blue. Length of cable run is limited by a maximum allowable voltage
drop, as explained in the Installation section of the applicable technical bulletin. Cable is resistant to
spread of fire. Supplied in 500-ft. (152m) spools. NEC/UL Listing is FPLR.
494467 Plenum Quad Trunk Cable (B6467)
Four-conductor trunk cable similar to 494465 Cable, but with Teflon (or equivalent) insulation for use
in plenums. Jacket color is red. Cable has fire-resistant and low-smoke-producing characteristics.
Supplied in 1000-ft. (304m) spools. NEC/UL Listing is FPLP.
493494 18/2 FPL White Cable
Cable consists of a white jacket over two #18 AWG solid conductors (yellow and blue). Used for making
branch connections to SIM sensors. Wire is resistant to spread of fire. Supplied in 1000 ft. spools.
NEC/UL Listing is FPL. Splice to Quad Trunk Cable using 809190 Scotchlok #558 connectors.
493493 Plenum FPFP 18/2 Red Cable
Two-conductor #18 AWG solid wire with yellow and blue insulation, similar to 493494 cable, but with
Teflon (or equivalent) insulation for use in plenums. Jacket color is red. Cable has fire-resistant and
low-smoke-producing characteristics. Supplied in 1000 ft. spools. NEC/UL Listing is FPLP. Splice to
quad trunk cable using 809190 Scotchlok #558 connectors.
493492 Wire
Single conductor (#16 AWG solid) wire, in a green jacket, used for making ground connections to the
control unit. Wire is resistant to spread of fire. Supplied in 100 ft. (30.4m) spools. NEC/UL Listing is
CL3.
494470 Cable (B6476-2)
Cable consists of two #18 AWG solid conductors (black and red) for connecting transformer power to
control or remote power supply. Cable comes with white sheath, is fire resistant and is supplied in 500-
ft. (152m) spools.
494481 Cable (6481)
Cable is used for wiring the operating panels to the RS-485 User Bus. Power-Limited Fire Protective
Signaling Circuit Riser Cable (FPLR), Class 3 Inside BA Riser Cable (CL3R). Cable consists of two
twisted pair #22 AWG wires and comes in a 500-foot spool. Jacket is beige and wire colors are black,
red, yellow, and blue.
Note: For other wire, refer to T-7 187 Common Equipment Technical Data Sheet.