FOCUS 200 PLUS Installation and Setup Guide
471943 Housing Unit
The 471943 Housing Unit is used to house one SIM gateway, one Micro PID, or one relay module.
Consists of a white plastic box with hinged cover (3-1/2" L x 3-l/2" W x 1-5/8" D).
472352 Housing Unit
The 472352 Housing Unit is used to house two SIM ateways, one PID gateway, two Micro PIDS, one
Quad PID, two COPIDS, two keyswitch interfaces, or a printer interface unit. Consists of a white
plastic box with hinged cover (9-1/4" L x 5" W x 1-5/8" D) (23.5cm x 12.78cm x 4.1cm).
248026 Assembly SPDT Relay Module
248309 SIM Relay Module Kit
494465 Quad Trunk Cable (B6465)
Four-conductor trunk cable (off white/sheathed, formerly blue) that is used for the RS-485 bus to
connect gateways, operating panels, and printer interface. It is also used for the gateway trunk.
Suitable for BA and FA applications. Consists of two #19 AWG and two #16 AWG solid conductors;
colors are black, red, yellow, and blue. Length of cable run is limited by a maximum allowable voltage
drop, as explained in the Installation section of the applicable technical bulletin. Cable is resistant to
spread of fire. Supplied in 500-ft. (152m) spools. NEC/UL Listing is FPLR.
494467 Plenum Quad Trunk Cable (B6467)
Four-conductor trunk cable similar to 494465 Cable, but with Teflon (or equivalent) insulation for use
in plenums. Jacket color is red. Cable has fire-resistant and low-smoke-producing characteristics.
Supplied in 1000-ft. (304m) spools. NEC/UL Listing is FPLP.
493494 18/2 FPL White Cable
Cable consists of a white jacket over two #18 AWG solid conductors (yellow and blue). Used for making
branch connections to SIM sensors. Wire is resistant to spread of fire. Supplied in 1000 ft. spools.
NEC/UL Listing is FPL. Splice to Quad Trunk Cable using 809190 Scotchlok #558 connectors.
493493 Plenum FPFP 18/2 Red Cable
Two-conductor #18 AWG solid wire with yellow and blue insulation, similar to 493494 cable, but with
Teflon (or equivalent) insulation for use in plenums. Jacket color is red. Cable has fire-resistant and
low-smoke-producing characteristics. Supplied in 1000 ft. spools. NEC/UL Listing is FPLP. Splice to
quad trunk cable using 809190 Scotchlok #558 connectors.
493492 Wire
Single conductor (#16 AWG solid) wire, in a green jacket, used for making ground connections to the
control unit. Wire is resistant to spread of fire. Supplied in 100 ft. (30.4m) spools. NEC/UL Listing is
CL3.
494470 Cable (B6476-2)
Cable consists of two #18 AWG solid conductors (black and red) for connecting transformer power to
control or remote power supply. Cable comes with white sheath, is fire resistant and is supplied in 500-
ft. (152m) spools.
494481 Cable (6481)
Cable is used for wiring the operating panels to the RS-485 User Bus. Power-Limited Fire Protective
Signaling Circuit Riser Cable (FPLR), Class 3 Inside BA Riser Cable (CL3R). Cable consists of two
twisted pair #22 AWG wires and comes in a 500-foot spool. Jacket is beige and wire colors are black,
red, yellow, and blue.
Note: For other wire, refer to T-7 187 Common Equipment Technical Data Sheet.
22-4