Figure 6-1: External Sounder Connections To The Bell Outputs - ADT FOCUS 200 PLUS Installation And Setup Manual

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
Installing an Alarm Housing
The 471956(7187-101) Alarm Housing and ADEMCO AB12 Bell are UL-approved exterior sounding
devices for local mercantile premises bell certification. For exterior auxiliary BA or FA bell applications,
U L
other sounding devices such as the 471859 (7187-037) Bell Unit may be used, provided applicable UL
installation guidelines are followed.
If 471956 Alarm Housing is being used, install it as follows:
Step
1
2
3
4
Wiring Bell Outputs
Wire sounding devices to the bell outputs as shown in Figure 6-1.
WIRING FOR
ADEMCO AB12
COMMERCIAL
BURGLARY
GRADE A BELL
Figure
If using the bell box tamper, program the option via the downline loader. Otherwise the system will not
detect a "short" on point 8.
6-6
Action
Mount the alarm housing on an outside wall of the building, visible from a public street. It
should be mounted at least 10 feet above street level, but no higher than the ceiling level
of the fourth story above street level.
Install the wiring between the control unit and the alarm housing in conduit, without
boxes or openings unless covers are tampered or welded to the box.
Using locally available caulking compound, caulk around the conduit connection at the
rear of the alarm housing to prevent water seepage into the housing.
If the alarm housing is flush-mounted, the building wall must include an opening 15"
(38.lcm) H x 24" (61cm) W x 5-1/2" (14cm) D with a louvered grille (provided by the
customer). Mount the housing within this opening, and affix a sign (supplied by the
customer) that prominently displays the words "BURGLAR ALARM."
AB12 BELL/BOX WIRING
2
3
4
1
TAMPER
SWITCHES
BELL
6-1: External Sounder Connections to the Bell Outputs
5
6
7
8
+
+
BELL 1
BELL 2
2k EOLR
AB12 WIRING NOTES:
• Disconnect the AB12's factory-wired
connection from its terminal #4 to its
outer box.
• Assign point 8 to a BA Group. Program
it as a Supervisory (SPV) Point Type.
• All wiring from AB12 to panel must be
run in conduit.
2k EOLR
5
6
AB12 OUTER BOX
INNER LINER
BELL 1 SHOWN AS A
BURGLARY BELL
OUTPUT WITH NON-
POLARIZED
INDICATING DEVICES.
BELL 2 SHOWN AS A
FIRE BELL OUTPUT
WITH POLARIZED
INDICATING DEVICES.