ADT FOCUS 200 PLUS Installation And Setup Manual page 215

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

WARNING: OWNER'S INSTRUCTION NOTICE NOT TO BE REMOVED
NOTES
REFER TO INSTRUCTIONS K3471 FOR ADDITIONAL INFORMATION
NOTE 1:
The combined standby current
BATTERY TABS
drawn from aux pwr #2, aux pwr #3
and aux relay terminal 10 (when
+
RED
wet) can not exceed 1.0A. The
combined alarm current drawn
from aux pwr #2, aux pwr #3, aux
-
BLK
relay terminal 10 (when wet), bell 1
and bell 2 cannot exceed 1.5A
when 443216 or N8167 transformer
is used, and 2.3A when 472404
POWER SWITCH
transformer is used.
NOTE 2:
Use 472411 2k EOLR for listed fire
installations. (supplied)
NOTE 3:
See instructions for max. # of
keypads and wire run length
restrictions.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
472404 wired-in
PROTECTION ASSOCIATION'S STANDARD 72,
transformer with
CHAPTER 3 (NATIONAL FIRE PROTECTION
enclosure
INPUT: 120VAC, 1.0A,
ASSOC., BATTERYMARCH PARK, QUINCY,
60Hz connect to a
443216 or N8167 plug-in
MA. 02269). PRINTED INFORMATION DESCRIBING
dedicated circuit
transformer (optional)
OUTPUT: 18VAC, 72VA
PROPER INSTALLATION, OPERATION, TESTING,
INPUT: 120VAC,
MAINTENANCE, AND REPAIR SERVICE IS TO BE
0.59A, 60 Hz connect
OUTPUT
to unswitched outlet
PROVIDED WITH THIS EQUIPMENT.
BL
BL
OUTPUT: 18VAC, 50VA
WH
BK
INPUT
TRNSFMR
1
NOTE:
443216 may not be used for listed commercial fire
installations. Total alarm current is limited to 1.5A.
Short pins 2 & 3 on P4.
472404 may be used for all listed commercial (burg,
fire, burg/fire) installations. Total alarm current is
limited to 2.3A, see note 1. Short pins 1 & 2 on P4.
WARNING:
THIS UNIT MAY BE PROGRAMMED TO
INCLUDE AN ALARM VERIFICATION
Connect to 12V, 7AH min/34.4AH max
FEATURE THAT WILL RESULT IN A DELAY
lead acid batteries using cables supplied.
OF THE SYSTEM ALARM SIGNAL FROM
See instructions for required capacity.
THE INDICATED FIRE CIRCUITS. THE
Float charging voltage: 13.7VDC. Battery
TOTAL DELAY (CONTROL UNIT PLUS
normally need not be replaced for
SMOKE DETECTORS) SHALL NOT EXCEED
at least 3 yrs. Battery connection is
60 SECONDS. NO OTHER INITIATING
supervised.
DEVICES SHALL BE CONNECTED TO
THESE CIRCUITS UNLESS APPROVED BY
THE LOCAL AUTHORITY HAVING
JURISDICTION.
P4
ON
1
CIRCUIT
CONTROL UNIT
2
(POINT)
OFF
3
JUMPER P4
ALARM CURRENT
Pins 1 & 2 shorted = 2.3A
Must use with 47204 transformer.
Pins 2 & 3 shorted = 1.5A
Must use with 443216/N8167
THE DELAY TIME MARKED ON THE INSTALLED
DETECTOR(S) IS TO BE USED
transformer.
JUMPER P3 Aux Relay Setting
Pins 1 & 2 shorted = wet
Pins 2 & 3 shorted = dry
GND
BELL OUTPUTS
AUX. RELAY
2
3
4
5
6
7
8
9
10
11
12
BELL 1
BELL 2
+
-
+
-
BELL
BELL
AUX RELAY (FORM C)
programmable response (not supervised)
HORN
HORN
WHEN WET: 12V terminal 10,
1.7A max., see note 1.
WHEN DRY: No voltage on terminal 10,
Contact Rating: 28V, 2A max.,
2k (note 2)
2k
resistive loads.
ALARM POLARITY SHOWN
FIRE CKTS: Supervise using 2k EOLR.
Use polarized sounding devices.
BURG CKTS: Supervision not req'd.
EOLRs not req'd. May use non
polarized devices. Ratings: 12VDC, 1.7A max.
See note 1. See instructions to enable/disable
supervision and for compatible devices.
FOCUS 200 PLUS SUMMARY OF CONNECTIONS
(472462)
AC
LED
TYPES OF FIRE SIGNALLING SERVICE:
Manual fire alarm, automatic fire alarm, sprinkler supervisory and waterflow alarm.
UL Listed local control (non-coded).
UL Listed central station, proprietary and Remote Station protected premises unit
when used with back-up dialer module. Installation limits under jurisdiction
of local authority.
BACK-UP LINE SEIZE
SMOKE DETECTOR
DELAY-SEC
MODEL DELAY-SEC
Attach 472402A
module to main
PCB using 3
standoffs
OPTIONAL 472402A BACK-UP DIALER MODULE
(supplied)
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM HEAD-
QUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH
THE APPROVAL OF THE LOCAL
AUTHORITY HAVING JURISDICTION.
P3
THE BURGLARY ALARM SIGNAL
1
SHALL NOT BE CONNECTED TO A
2
POLICE EMERGENCY NUMBER.
3
RS-485 #1
RS-485 #2
POINT 1
17
18
19
20
21
22
23
24
25
26
+
-
+
-
Blue Yel Red Blk
Blue Yel Red Blk
+
-
AUXILIARY POWER #2 & #3
(Not Supervised)
Rating: 12VDC, 1.0A max.
SMOKE
See note 1.
POINT 1-8 NOTES
N.C.
N.C.
• All points provide Style B supervision
• Point resistance (excluding EOLR):
- Points 1, 2: 100 ohms max
N.O.
- Other points: 300 ohms max
• Point response: 350 - 500mS (all points)
2k (note 2)
• Ratings for points 1, 2:
- 10 - 14VDC
- 2mA max for smoke det. (up to 16 detectors
of the type specified in the instructions
can be used)
• UL compatibility ID: A
Do not mix fire and burg. sensors on one loop.
N.C. contacts for burg. usage only.
TEST BURGLARY SYSTEM WEEKLY
The 472402A Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398U-68628-MO-N
LED (GREEN)
Ringer Equivalence: 0.7B
BACK-UP
PHONE JACK
RJ31X
SEE TELCO
JACK SHOCK
WARNING
Connect to main PCB
BELOW
header J6 using ribbon
cable (supplied)
(connect using supplied cable)
Supervision is programmable
BACK-UP TLM ON HOOK
BACK-UP DIALER EARTH
VOLTAGE THRESHOLD (BLUE)
GROUND SCREW
INTACT: 25V
(wire to main PCB,
terminal 3 or 4)
CUT:
13V
The Focus Built-in Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398R-68192-AL-E
Ringer Equivalence: 0.7B
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
POINT 2
POINT 3
POINT 4
POINT 5 POINT6
POINT 7 POINT 8
27
28
29
30
31
32
33
34
35
36
38
37
+
-
+
-
+
-
-
+
-
+
+
-
SMOKE
N.C.
N.C.
N.C.
N.C.
N.C.
N.O.
N.O.
N.O.
N.O.
N.O.
N.O.
2k
2k
2k
2k
2k
2k
Bell Box
Points 3 & 4 may
Tamper
be set for a Style "D"
configuration.
J5
J5 VOLTAGE TRIGGERS
(not supervised)
1
See instructions for trigger use
2
and programming.
3
Make connections
1. GROUND (BLACK)
4
using 472412 cable
2. OUT 1
(BLUE)
5
(not supplied)
3. OUT 2
(BROWN)
6
4. OUT 3
(GREEN)
7
5. OUT 4
(RED)
8
9
6. OUT 5
(WHITE)
7. OUT 6
(YELLOW)
8. OUT 7
(GRAY)
Cabinet
9. OUT 8
(VIOLET)
Tamper
Ratings:
Input
Low Output: 0.7V thru 100 ohm
can sink 33mA with 4V drop
High Output: 12V thru 4k ohm
MAIN DIALER
LED
J6
1
2
3
Backup Dial Header472402A
4
5
or AC communication module
6
472491 Jack
7
8
9
Connect
MAIN
SERVICE
RJ31X using
cable supplied.
RJ31X
Supervision is
39
40
programmable.
JACK
PHONE JACK
WARNING: TO PREVENT
RISK OF ELECTRICAL SHOCK,
DISCONNECT TELCO JACK
BEFORE SERVICING THIS PANEL.
-
+
ALL CIRCUITS ARE POWER
LIMITED EXCEPT THE OUTPUT
N.C.
OF THE 472404 TRANSFORMER
N.O.
2k