ADT FOCUS 200 PLUS Installation And Setup Manual page 138

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
Entry
Number
3 (MD)
U L
Entry delay must not exceed 45 seconds for all UL certified installations.
Entry
Number
4 (FL)
5 (MID)
6 (VVS)
13-2
Description
Function
Assigned to points where sensors are installed in the entry/exit path
Movable
Delayed
to allow the customer time to enter or exit the premises without
creating an alarm.
A programmable entry/exit delay time is provided, during which the
control unit does not acknowledge an alarm condition from a movable
delayed sensor in the entry/exit path.
The point does not produce an alarm if proper entry and exit
procedures are followed; only the operating panel sounder
annunciates the delay.
Description
Function
Fixed Local
This point assignment locally annunciates an alarm in Day or Nite
Set, but no CCC transmission of an alarm condition is sent at any
time. However, a trouble condition initiates a trouble signal to the
CCC during Day Set, and an alarm transmission during Nite Set.
Movable
This point assignment causes local annunciation of an alarm in Day
Set (no CCC transmission).
Instant
Daytime
During Nite Set, the instant daytime annunciation protection reacts
Annunciation
the same as movable instant protection. Example of application: local
annunciation of emergency exit door without initiation of a CCC
transmission during Day Set.
Vault
Points assigned to the vault vibration sensor category operates as BA
Vibration
movable instant protection points, but follows the on/off status of
BA1. When BA1 is off, the VVS points in BA2 through BA8 are
Sensor
bypassed and remain so until BA1 is closed.
If manually bypassed from an operating panel (bypass option has
been selected and Bypass, VVS has been entered at operating panel),
all VVS sensors in all BA groups become bypassed. They remain in
this condition until:
1
The VVS bypass condition is manually restored to normal at the
operating panel.
2
Either the BA1 latest scheduled close time is reached or
midnight is reached, whichever occurs sooner.
Turning the protection Off for a given BA group does not unbypass
any VVS points in that group that was VVS bypassed.
The purpose of this point designation is to avoid the possibility of
false alarms during the open period of a bank due to vibration and
noise created by nearby construction, traffic conditions, etc. The
vault(s) involved are not completely unprotected because the vault
door contacts and other vault protective devices are in-circuit as long
as the associated BA group is turned on.
Note: If this type of bypass control is unsatisfactory, then points with
vault vibration sensors should be programmed as movable instant
points, in which case they follow the status of the assigned BA group
rather than the status of BA1.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents