ADT FOCUS 200 PLUS Installation And Setup Manual page 129

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

3.
In table 6, enter devices connected to Auxiliary Relay (if used for wet operation). Calculate standby
and alarm currents, then add to get Auxiliary Relay current subtotal.
Table 6: AUXILIARY RELAY CURRENT LOAD
Device Model #
4.
In table 7, enter devices connected to Bell 1 output. Calculate alarm currents, then add to get Bell
1 output current subtotal.
Table 7: BELL 1 OUTPUT CURRENT LOAD
Device Model #
Device Current X # of Units =
Auxiliary Relay Subtotal
(terminal 10)1.7 amp max
(If setup for wet operation)
Device Current X # of Units =
Bell 1 Output Subtotal
(terminals 5 & 6) 1.7 amp max
Section 12 – Power Requirements
Total Current
Standby
Alarm
Total Current
Standby
Alarm
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
XXXXXX
12-11