Summary Of Connections Diagram - ADT SA10ADTEG Programming Manual

For standard controls. safewatch pro & security manager.
Hide thumbs Also See for SA10ADTEG:
Table of Contents

Advertisement

BATTERY FUSE
(e.g. ADEMCO No. 90-12)
GEL LEAD ACID TYPE.
FOR REPLACEMENT
BATTERY NORMALLY NEED NOT BE
USE SAME VALUE
REPLACED FOR AT LEAST 3 YRS.
BATTERY CAPACITY FOR EMERGENCY
STANDBY USE AT LEAST 4 HOURS.
BATTERY
BLACK
12V, 4AH
+
(e.g. ADEMCO
RED
No. 467)
OR 12V, 1.2AH
BATTERY
CHARGING
CONNECTOR TABS
VOLTAGE
13.8VDC
RED
TO DETERMINE TOTAL
JUMPER
STANDBY LOAD ON
CUT FOR BELL SUPERVISION
BATTERY, ADD 100mA
TO TOTAL OFAUX.
POWER OUTPUT AND
1
2
3
REMOTE TOUCHPAD
CURRENTS.
USE UL LISTED LIMITED
ENERGY CABLE FOR
ALL CONNECTIONS
PLUG-IN
TRANSFORMER
16.5VAC, 25VA
TO 110VAC
(e.g. ADEMCO
UNSWITCHED OUTLET
No. 1321.
(24-HR)
+
ALARM OUTPUT
10.5–13.8VDC, 2A MAX.
(600mA MAX. FOR UL USAGE,
INCLUDING AUX. POWER)
STEADY FOR BURGLARY/PANIC,
TEMPORAL SOUNDING FOR FIRE (e.g.
USE ADEMCO No. 740 SOUNDER,
Nos. 702 OR 719 SIREN, OR 12V BELL)
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE
ALARM HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE PERMISSION
OF THE LOCAL AUTHORITY HAVING JURISDICTION.
THE BURGLAR ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY NUMBER.
THESE OPTIONAL ITEMS
MAY ALSO BE USED
SEE THEIR INSTRUCTIONS
ADEMCO No. 5800TM
TRANSMITTER MODULE
(20mA)
(for No. 5827BD
3A
Wireless Bidirectional Touchpad)
AND/OR
ADEMCO No. 4285
VOICE MODULE (160mA)
AND/OR
ADEMCO No. 7720PLUS
+
or 7820 LONG RANGE RADIO
BLK
RED
GRN
YEL
4
5
6
7
8
+
AUX. POWER
OUTPUT
10.5-13.8VDC
500mA MAX.
INTERRUPTS
FOR FIRE
ALARM RESET
NOTE:
TOUCHPAD
CURRENT
MUST BE
INCLUDED
IN AUX.
CURRENT
DRAIN
CALCULATIONS
1000
OHMS
EOLR
REMOTE
• MAXIMUM LOOP RESISTANCE (EACH ZONE): 300 OHMS (PLUS EOLR)
TOUCHPAD(S)
• RESPONSE, ZONES 1–6: 300–500MSEC
REMOTE TOUCHPADS
• ZONE 3 CAN BE PROGRAMMED FOR N.C. SENSOR FAST RESPONSE
TO AN OPEN: 10MSEC MAX
SYSTEM MUST BE
PROGRAMMED WITH A
• ZONE 5 CAN BE PROGRAMMED FOR USE AS A FIRE ZONE.
CUSTOM ENGLISH
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
TOUCHPAD, BUT NEED NOT
OPERATION IS SUBJECT TO THE FOLLOWING TWO
REMAIN IN THE SYSTEM.
CONDITIONS: (1) IT MAY NOT CAUSE HARMFUL INTERFERENCE,
AFTER PROGRAMMING, THE
(2) IT MUST ACCEPT ANY INTERFERENCE THAT MAY CAUSE
SYSTEM CAN USE:
UNDESIRED OPERATION.
6128ADT (30mA) OR
6139ADT (100mA).
MULTIPLE TOUCHPADS MAY BE
USED, BUT USE MAX. OF 220 FT.
OF #22 WIRE OR 550 FT. OF #18.
OPTIONAL
FOR UP TO 16 RF EXPANSION ZONES
ADEMCO 5881 Type
RF RECEIVER
WIRELESS ZONES
5881L: UP TO 8
5881M/5881H: UP TO 16
SET UNIT'S DIP SWITCH
FOR DEVICE ADDRESS OF "0"
(See receiver's instructions)
OPTIONAL
ADEMCO No. 4204
RELAY MODULE (180mA MAX)
(4 OUTPUT RELAYS)
SET UNIT'S DIP SWITCH
FOR DEVICE ADDRESS OF "1"
(See unit's instructions)
9
10
11
12
13
14
1000
1000
1000
1000
OHMS
OHMS
OHMS
OHMS
EOLR
EOLR
EOLR
EOLR
COMPLIES WITH FCC RULES, PART 68
FCC REGISTRATION NO. AC398U-68192-AL-E
RINGER EQUIVALENCE: 0.7B.
AUX PWR
+
5
OUTPUT
BLK
-
TERMS
4
+
-
VIOLET
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
1000
OHMS
EOLR
+
+
HEAT
DETECTOR
-
ZONE 5
(IF PROGRAMMED FOR FIRE)
15
16
17
18
19
20
TIP
RING
TIP
RING
(BROWN)
(GRAY)
(GREEN)
(RED)
INCOMING
HANDSET
PHONE
LINE
TELEPHONE WIRING
(VIA RJ31X JACKAND
DIRECT CONNECT CORD)
WARNING: TO PREVENT RISK OF
SHOCK, DISCONNECT TELEPHONE
LINE AT TELCO JACK BEFORE
SERVICING THIS UNIT.
THIS EQUIPMENT SHOULD BE INSTALLED IN
1000
OHMS
ACCORDANCE WITH THE NATIONAL FIRE
EOLR
PROTECTION ASSOCIATION'S STANDARD 74
(NATIONAL
FIRE
PROTECTION
BATTERYMARCH PARK, QUINCY, MA 02269).
PRINTED INFORMATION DESCRIBING PROPER
INSTALLATION,
OPERATION,
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
WARNING:
OWNER'S INSTRUCTION
NOTICE NOT TO BE REMOVED. WEEKLY
TESTING IS REQUIRED ENSURE PROPER
OPERATION OF THIS SYSTEM.
+
RED
EOL
POWER
SUPER-
VISION
RELAY
MODULE
A77-716B
LOCATED
AT LOWER
RIGHT OF
CIRCUIT
BOARD
21
EARTH
GROUND
TERMINAL
PROPER
EARTH
GROUND
(SEE
INSTRUCTIONS)
ASSOC.,
TESTING,

Advertisement

Table of Contents
loading

Table of Contents