Advertisement

5 Setup and Wiring
Connection of Terminal Block of FH-1000/2000/3000/5000 Series
Connecting of Sensor Controller's terminal block in order to connect package the terminal block con-
nector (male; FH-XCN).
Use the specified wire size (AWG10 to 16) and keep the power supply wires as short as possible
(Max. 2 m).
1
Insert the end of the signal line (electric wire) into the terminal block connector (male), and
tighten the three screws on the connector top to fix the wire. Recommended tightening torque:
0.7-0.8 N•m
2
Connect the wire and power source to the terminal block connector (male) depending on the
indicated terminal block connector.
Indicate of terminal
block connector
3
Insert the terminal block connector (male) to the terminal block connector (female) of Sensor
Controller.
4
Tightens and fix the left and right screws for the terminal block connector (male). (Recommend-
ed tightening torque: 0.7 to 0.8 N•m)
5 - 6
+
Connect the DC output positive (+V) of 24 VDC power.
-
Connect the DC output positive (-V) of 24 VDC power.
Connect the earth.
Terminal block connector (female)
Terminal block connector (male)
Function
FH Series Vision System Hardware Setup Manual (Z366-E1)