Et 200Sp As A Dp Slave - Siemens SIMATIC ET 200SP System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

10.3.3

ET 200SP as a DP slave

Configuration example
To use the ET 200SP distributed I/O system as a DP slave, you need the IM 155-6 DP HF.
Figure 10-6
Commissioning procedure
To commission the ET 200SP distributed I/O system as a DP slave on PROFIBUS DP, we
recommend the following procedure:
Table 10- 6
Step
1
2
3
4
5
6
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF
ET 200SP as a DP slave
Procedure for commissioning the ET 200SP as a DP master for PROFIBUS DP
Procedure
Installing ET 200SP (with
IM 155-6 DP HF)
Setting the PROFIBUS address on the
interface module
Connecting ET 200SP
Supply voltages
PROFIBUS DP
Sensors and actuators
Configuring DP master (including
PROFIBUS address)
Switching on supply voltages for DP
master
Switching on supply voltages for DP
slaves
10.3 Commissioning the ET 200SP on PROFIBUS DP
See ...
Section Installation (Page 39)
Section Interface module
(http://support.automation.siemens.com/W
W/view/en/55683316/133300)
Section Wiring (Page 49)
Documentation of the DP master
Documentation of the DP master
Interface module
(http://support.automation.siemens.com/W
W/view/en/55683316/133300) Manual
Commissioning