Commissioning

10.4 Startup of the ET 200SP with empty slots

Step
7
8
9
10
10.4
Startup of the ET 200SP with empty slots
Procedure
You can configure the ET 200SP distributed I/O system with any number of empty slots.
To build the ET 200SP distributed I/O system with any number of empty slots, follow these
steps:
1. Cover all empty slots with BU covers.
2. Finish the configuration with a server module.
Special consideration: A "Module missing in slot x" diagnostic message is generated by the
CPU/interface module for empty slots in which I/O modules are configured.
10.5

Removing/inserting a SIMATIC memory card on the CPU

Requirement
The CPU only supports pre-formatted SIMATIC memory cards. If necessary, delete all
previously stored data before using the SIMATIC memory card. Additional information about
deleting the contents of the SIMATIC memory card can be found in the section, SIMATIC
memory card - overview (Page 196).
In order to work with the SIMATIC memory card, first ensure that the SIMATIC memory card
is not write-protected. If it is, move the slider out of the lock position.
180
Procedure
Download configuration to the DP mas-
ter
Switching DP master to RUN
Checking LEDs
Testing inputs and outputs
See ...
STEP 7 online help
Documentation of the DP master
Interface module
(http://support.automation.siemens.com/W
W/view/en/55683316/133300) Manual
The following functions are helpful: Monitor-
ing and modifying tags, testing with program
status, forcing, controlling the outputs. Refer
to section Test functions and eliminating
problems (Page 224)
System Manual, 12/2015, A5E03576849-AF
Distributed I/O system