Required accessories
● If you use Fast Connect Cable, we recommend the Industrial Ethernet Fast Connect
Stripping Tool (6GK1901-1GA00) with green knife cassette (6GK1901-1B...). This
guarantees fast and safe stripping.
● Fast Connect Cable (recommended types):
– IE FC TP Standard Cable GP 2x2 (6XV1840-2AH10)
– IE FC TP Trailing Cable 2x2 (6XV1840-3AH10)
– IE FC TP Marine Cable (6XV1840-4AH10)
– IE FC TP Flexible Cable GP 2x2 (6XV1870-2B)
– IE FC TP Trailing Cable 2x2 (6XV1870-2D)
– IE TP Torsion Cable 2x2 (6XV1870-2F)
– FC TP FRNC Cable GP (6XV1871-2F)
– IE FC TP Food Cable GP 2x2 (6XV1871-2L)
– IE FC TP Festoon Cable 2x2 (6XV1871-2S)
● Please refer to the specifications in the PROFINET Installation Guide
(http://www.profibus.com).
Procedure
Watch the video sequence (http://support.automation.siemens.com/WW/view/en/95886218)
To connect PROFINET IO to the CPU/interface module via the BA 2xFC BusAdapter, follow
these steps:
1. Strip the sleeve of the PROFINET connecting cable as follows:
Figure 5-12
2. Pull back the locking slide and fold up the cover of the connection element.
3. Pull up the wire guide as far as it will go.
4. Insert the unstripped single wires of the PROFINET connecting cable (according to the
attached color coding) into the wire guide and press the guide down firmly as far as it will
go.
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF
PROFINET connecting cable
5.9 Connecting interfaces for communication
Wiring
71