Advertisement

Commissioning
10.3 Commissioning the ET 200SP on PROFIBUS DP
10.3.3

ET 200SP as a DP slave

Configuration example
To use the ET 200SP distributed I/O system as a DP slave, you need the IM 155-6 DP HF.
Figure 10-6
Commissioning procedure
To commission the ET 200SP distributed I/O system as a DP slave on PROFIBUS DP, we
recommend the following procedure:
Table 10- 6
Step
1
2
3
4
5
6
7
208
ET 200SP as a DP slave
Procedure for commissioning the ET 200SP as a DP master for PROFIBUS DP
Procedure
Installing ET 200SP (with IM 155-6 DP HF)
Setting the PROFIBUS address on the interface
module
Connecting ET 200SP
Supply voltages
PROFIBUS DP
Sensors and actuators
Configuring DP master (including PROFIBUS
address)
Switching on supply voltages for DP master
Switching on supply voltages for DP slaves
Download configuration to the DP master
See ...
Section Installation (Page 54)
Section Interface module
(http://support.automation.siemens
.com/WW/view/en/55683316/1333
00)
Section Wiring (Page 75)
Documentation of the DP master
Documentation of the DP master
Interface module
(http://support.automation.siemens
.com/WW/view/en/55683316/1333
00) Manual
STEP 7 online help
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG