Display Of Measurands - Siemens SICAM MMU 7KG9663 Device Manual

Table of Contents

Advertisement

4.2

Display of Measurands

Table 4-4
Measurands
Measurands
Voltage V
ph-ph
(delta)
Acc. to parameterization
Voltage V
ph-N
(star)
Acc. to parameterization
Voltage harmonics HV
ph
Voltage unbalance V
unbal
Angle between the phase-
ground voltages a-b
ϕab
Angle between the phase-
ground voltages a-c
ϕac
Current I
Acc. to parameterization
Current harmonics HI
ph
Current unbalance I
unbal
Active power P
+ demand, - supply
Reactive power Q
+ inductive, - capacitive
Apparent power S
3)
Power factor PF
Active power factor cos ϕ
3)
Phase angle ϕ
Frequency f
Active energy WP demand
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Unit
V
AC 110 V
AC 190 V
AC 400 V
AC 690 V
V
AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
V
2nd to 21st Harmonics
%
-
Degree
-
Degree
-
A
AC 1 A
AC 5 A
A
2nd to 21st Harmonics
%
-
W
-
var
-
VA
-
-
-
3)
-
-
Degree
-
Hz
50 Hz and 60 Hz
Wh
-
Rated Value
(max. AC 600 V for UL)
(max. AC 347 V for UL)
4 Measurands and Characteristics
4.2 Display of Measurands
Operat. Measurem. Uncertainty
acc. to
acc. to
1)
IEC 61557-12
IEC 60688
±0.2 %
±0.1 %
±0.2 %
±0.1 %
±0.5 %
±0.5 %
±0.2 %
±0.2 %
±2°
±1°
±2°
±1°
±0.2 %
±0.1 %
±1 %
±1 %
±0.2 %
±0.2 %
±0.5 %
±0.2 %
0,2S acc. to
IEC 62053-21
±0.5 %
±0.2 %
±0.5 %
±0.2 %
±1 %
±0.5 %
±1 %
±0.5 %
±2°
±1°
See Table 4-5
See Table 4-5
±0.5 %
±0.5 %
2)
35

Advertisement

Table of Contents
loading

Table of Contents