Starting The Device With The Default Ip Address - Siemens SICAM MMU 7KG9663 Device Manual

Table of Contents

Advertisement

5.7.3

Starting the Device with the Default IP Address

SICAM MMU has the following internal default IP address: 192.168.0.55.
If you have entered a custom IP address during device configuration, you can temporarily activate the internal
default IP address of the device if necessary. Do so by pressing the IP-Addr. push-button on the DIN rail side
of the device for at least 3 s with the device switched on.
Fig. 5-5
When you press the IP-Addr. push-button, SICAM MMU will reset and use the default IP address until you have
set a new IP address or switched the device off and on again.
NOTE
Changing the IP address will lead to a device reset, and the LEDs on the top side of the device indicate that
the device was started with the default IP address (see chapter 12.3).
In this case, the parameterized IP address and the default IP address are displayed on the Information tab,
Device information item (see chapter 7.2.5).
When the device has started with the default IP address, the factory-set default passwords are also active (see
chapter 7.3.4.4).
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Location of the Push-button for Activating the Default IP Address
IP-Addr. push-button for
default IP address
Default IP Address : 192. 168.0.55
Default Subnet Mask : 255.255 .255.0
5 Getting Started
5.7 Commissioning
53

Advertisement

Table of Contents
loading

Table of Contents