7 Operation
7.3 Configuration of the Device
7.3.4

Setting Administrative Parameters

In the Configure tab you can view, and if necessary, edit the administrative settings. You can select the pa-
rameters in the Administrative menu in the navigation window. You can enter the settings in the input/output
windows Time synchronization, Communication Ethernet, IEC 60870-5-104 (only if this bus protocol was
selected under Communication Ethernet), and Device and language.
NOTE
Observe the procedure for the device configuration described in chapter 7.3.1 when setting the administrative
parameters.
7.3.4.1 Time Synchronization
Default Settings and Setting Ranges of the Time Synchronization
Table 7-7
Source time synchronization
Time zone offset to UTC
Daylight Saving Time switchover
DST offset to UTC
Start of DST
End of DST
Primary NTP server IP address
Secondary NTP server IP address
Error indication after
108
Time Synchronization Settings
Parameter
Additional Parameters if the Source is Ethernet NTP
(Modbus TCP and IEC 60870-5-104)
Default Setting
Internal
+00:00
yes
+01:00
March
Last week
Sunday
02:00 AM
October
Last week
Sunday
03:00 AM
192.168.0.254
192.168.0.253
10 min
Setting Range
Acc. to list box
(see chapter 15)
-12 to +13 (hours)
(in increments of 0.5 h)
no
yes
0 to + 2 (hours)
(in increments of 0.5 h)
Acc. to list boxes
(see chapter 15)
Acc. to list boxes
(see chapter 15)
Any
Any
No polling of the NTP server if
0.0.0.0 was entered
2 min to 120 min
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016