Calibrating The Alternating-Voltage Measuring Range - Siemens SICAM MMU 7KG9663 Device Manual

Table of Contents

Advertisement

10.2

Calibrating the Alternating-Voltage Measuring Range

Measurement Setup
Fig. 10-1
Calibration is only possible with symmetrical phases (3 x 120°), see figure 10-1.
Measuring Ranges
You can perform the calibration for the following alternating-voltage measuring ranges:
AC 63.5 V
AC 110 V
AC 230 V
AC 400 V
Calibration
To calibrate the alternating-voltage measuring ranges, proceed as follows:
Set up the measurement as shown in figure 10-1, depending on the device variant.
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Measurement Setup for Calibrating the Alternating-Voltage Measuring Range
10.2 Calibrating the Alternating-Voltage Measuring Range
Reference
Voltage
Output
1
2
3
N
10 Calibration
201