12 Failures and LED Indications
12.2 Commissioning during Failures
Wait for at least 20 s and then click the home link.
The User Interface opens.
Starting User Interface with Loading a New/Different Firmware
Click the Browse... button.
The Choose file dialog box opens.
In the Choose file dialog box select the current firmware update (file extension .pck) in the Look in: list
box and click the Open button.
The path appears in the Browse... field.
Click the upload button.
The firmware is uploaded from the device to the PC and the following information is displayed in the Boot
Loader window:
Fig. 12-3
Wait for at least 30 s and then click the home link.
The User Interface opens.
12.2.2

Manual Start of the Boot Loader

If it is necessary to start the Boot Loader manually, proceed as follows:
If the SICAM MMU is still energized by the supply voltage, switch off the supply voltage.
Press the IP-Addr. push-button at the SICAM MMU (see chapter 5.7.3), and holding the IP-Addr. push-
button down, switch on the supply voltage.
Hold the IP-Addr. push-button down until the LEDs ERROR (red) and H2 (yellow) on the device top side
are lit (LEDs RUN (green) and H1 (yellow) are off).
Release the IP-Addr. push-button.
SICAM MMU starts the Boot Loader with the Boot Loader HTML page (see figure 12-1).
220
Information in the Boot Loader
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016