5 Getting Started

5.2 Assembly

5.2
Assembly
5.2.1

General Assembly Notes

SICAM MMU is intended to be installed on a DIN rail, e.g. in a control cabinet.
WARNING
Do not touch any live parts.
Non-observance may lead to death or serious injury.
After installation of the device and wiring, close the control cabinet.
The installation site must be vibration-proof. The permitted ambient temperature must be observed (see
the technical data in chapter 13).
Operating the device outside the permitted operating temperature range can lead to measuring errors and
device failure.
The terminals are designed for wire cross-sections of 2.5 mm² max.
The device must not be exposed to condensation during operation.
The device must be installed in a location where it is not exposed to direct sunlight and strong temperature
variations.
44
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016