11 Maintenance, Storage, Transport

11.1 Maintenance

11.1
Maintenance
Except for a battery replacement, the SICAM MMU is maintenance-free.
Wipe the device using a clean, dry and soft cloth if necessary. Do not use solvents.
The Product Information enclosed with the device (ordering code E50417-B1050-C514) describes how to re-
place the battery.
11.2

Storage

Store the device in a dry and clean location. Store the device within a temperature range from -25 °C to +70 °C
(-13 °F to +158 °F).
The relative humidity must not lead to condensation or ice formation.
To avoid premature aging of the electrolytic capacitors, store the device within the recommended temperature
range of +10 °C to +35 °C (+50 °F to +95 °F).
Siemens furthermore recommends connecting the device to supply voltage once a year for 1 to 2 days in order
to form the inserted electrolytic condensers. This procedure should also be carried out before operating the
device.
NOTE
In this context, pay attention to the commissioning notes in chapter 5.7.
The Lithium-batteries in our equipment are subject to Special Provision 188 of the UN Recommendations on
the Transport of Dangerous Goods Model Regulations and Special Provision A45 of the IATA Dangerous
Goods Regulation and the ICAO Technical Instructions. This is only valid for the original battery or original
spare batteries.
11.3

Transport

If devices are to be shipped elsewhere, you can reuse the transport packaging. When using different packag-
ing, you must ensure that the transport requirements according to ISO 2248 are adhered to. The storage pack-
ing of the individual devices is not adequate for transport purposes.
216
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016