Ethernet Communication - Siemens SICAM MMU 7KG9663 Device Manual

Table of Contents

Advertisement

15.3.2

Ethernet Communication

15.3.2.1 General Settings
1)
IP Address
Subnet mask
Default gateway
Enable SNMP
Bus protocol
1)
After the parameter changes have been enabled, the device resets.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
15.3.2.2 Ethernet Communication with Bus Protocol Modbus TCP
Use a user-port number
User-port number
(can only be set when Use a user-port
number is parameterized with yes)
Access rights for user port
(can only be set when Use a user-port
number is parameterized with yes)
Access rights for user port 502
Keep Alive time
Communication supervision time
1)
After the parameter changes have been enabled, the device resets.
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Parameter
1)
1)
Parameter
1)
1)
Default Settings
192.168.0.55
255.255.255.0
192.168.0.1
no
Modbus TCP
Default Settings
no
10000
Full
Full
10 s
600 * 100 ms
15 Operating Parameters
15.3 Administrative
Setting Range
Any
0.0.0.0 = DHCP
Any
Any
no
yes
2)
-none-
Modbus TCP
IEC 60870-5-104
Setting Range
no
yes
10000 to 65535
Full
Read only
Full
Read only
0 s = switch off
1 s to 65 535 s
0 s = none
100 ms to 6 553 400 ms
249