Test Data; Electrical Tests - Siemens SICAM MMU 7KG9663 Device Manual

Table of Contents

Advertisement

13.2

Test Data

Reference Conditions for Determining the Test Data
Input current
Input voltage
Frequency
Curve shape
Ambient temperature
Supply voltage
Warm-up time
Interfering fields
13.2.1

Electrical Tests

Standards
Standards:
Insulation Test according to IEC 61010-1
Inputs/Outputs
Current measuring inputs
Voltage measuring inputs
Supply voltage
Binary outputs
Ethernet interface
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Rated current ± 1 %
Rated voltage ± 1 %
45 Hz to 65 Hz
Sine, total harmonic distortion ≤ 5 %
23 °C ± 1 °C
V
± 1 %
HN
≥ 15 min
None
IEC 60688 and IEC 60255
IEEE Std C37.90, see individual functions
VDE 0435
For more standards see also individual functions
Insulation
Rated
Voltage
Reinforced
150 V
Reinforced
480 V
Reinforced
300 V
Reinforced
300 V
Function
< 50 V
13 Technical Data
13.2 Test Data
ISO Test Voltage
Category
AC 2.3 kV
Cat. III
Surge voltage
Cat. III
9.76 kV
DC 3.125 kV
Cat. III
AC 3.536 kV
Cat. III
DC 700 V
Cat. III
233