Parameter
Parameter
Room tmp setpoint
Start stpt cooling
Start stpt heating
Hysteresis
Compensation time
Prerequisite
Enable
Parameter
Damper
Fire damper
Configuration
Parameter
Damper fdbk
Fire damper fdbk
Parameterization
Parameter
Off delay by fanoff
46 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 46
BDCX.100820.01GB
Building Technologies
Main Index > Unit > Operating mode > Tmp start
Range
-64.0...64.0 [°C]
-64.0....64.0 [°C]
-64.0...64.0 [°C]
0.1...64.0 [°C]
0...999 [min]
5.2.9
Optimum Start Stop Function
Not yet available.
5.3

Damper control

5.3.1
General
Dampers are enabled in configuration 1, configuration 2 and configuration I/Os,
preconfigured and the inputs, outputs defined.
Main Index > Configuration > Configuration 1
Range
– No
– Combined
– Supply
– Supply+Exh
– No
– Yes
– FollowUnit
Main Index > Configuration > Configuration 2
Range
– No
– One
– Two
– Closed
– Clsd+Opnd
– Combined
Main Index > Unit > Damper Control
Range
0...36000 [s]
Standard application AHU
Functions
Function
Boost room setpoint.
Start temperature for cooling.
Start temperature for heating.
Shutdown hysteresis.
Time by which plant start is advanced.
Function
– No opening/closing of dampers.
– Two dampers with common output.
– Outside air damper with output.
– Two dampers with separate outputs.
– No fire dampers.
– Fire dampers.
– Fire dampers are opened with Unit Start or
closed with Unit Stop.
Function
– No damper feedback.
– Feedback for outside air dampers (or a common
feedback for both dampers).
– Separate feedback for outside air and exhaust air
damper.
Fire damper feedback.
– Only one feedback for close.
– Two separate feedbacks for open and close.
– Two feedbacks for open and close, but only one
signal. The syntax must be correct:
1 (close) ---> 0 (moving) ---> 1 (open)
Function
Switch-off delay for outside air, exhaust and fire
dampers. The dampers are closed after this period
after switching off the supply air fan.