17.13 Damper Control - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Damper control
Parameter
Function
Off delay by fanoff
Delay Off Time for Supply, Exhaust and Fire
damper
Damper
Jumpline to Supply and Exhaust Damper
settings
Fire damper
Actual Command; Jump line to Fire damper
settings
Main Index > Unit > Damper Control > Damper
Parameter
Function
Outside air cmd
Command Outside air Damper (combined
Damper)
Outside air fdbk
Outside air Damper Feedback (combined
Damper)
Outs offby fdbk alm
Take akway Command in case of Feedback
alarm
StrtUpDly outs fdbk
Delay time until Feedback = 1
Extract air cmd
Command Extract Damper (combined
Damper)
Extract air fdbk
Extarct Damper Feedback (combined
Damper)
Extr offby fdbk alm
Take akway Command in case of Feedback
alarm
StrtUpDly Extr fdbk
Delay time until Feedback = 1
Opening time
Default Open time for Dampers if no real
Feedback
Main Index > Unit > Damper Control > Fire damper
Parameter
Function
Command
Command Fire damper
Feedback opened
Feedback Damper opened
Feedback closed
Feedback Damper closed
No move
Message if Damper do not follow Command Ok...ALarm
State
State of the Fire damper
Mode
Operation Mode Fire damper
Opening time
Open Time for Fire damper
Closing time
Close Time for Fire damper
Start manual test
Direct start from Auto Test over HMI
Auto Test
Date and Time for Auto Test
auto test interval
Interval for Auto Test
194 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 194
BDCX.100820.01GB
Building Technologies

17.13 Damper control

17.13.1 Start page
17.13.2 Damper
17.13.3 Fire damper
Standard application AHU
HMI
Value range
Unit
0...36000
--- S ---
On...Off
Value range
Unit
On...Off
No...Yes
No...Yes
0...36000
--- S ---
On...Off
No...Yes
No...Yes
0...36000
--- S ---
0...36000
--- S ---
Value range
Unit
On...Off
OK...No
Ok...No
NDef
Clsd
Move
Opnd
NDef
Ok
Debug
Alm
0...36000
--- S ---
0...36000
--- S ---
Passive
Aktive
0...3600
h
Standard
R S Link
10
6
6
Section:
5.3.1
6
Standard
R S Link
X
X
Yes
6
180
6
Section:
X
5.3.2
X
Yes
6
180
6
20
6
Standard
R S Link
X
X
X
X
X
X
Section:
5.3.3
6
6
Passive
6
6
6
CE1P3977en_02