Main Index > Unit > Outputs > Digital outputs > Element > Priority array
Parameter
Function
Default
Replacement value, when no priority is
active.
Prio 01
Value for priority 1.
...
...
Priority 16
Value for priority 16.
Main Index > Unit > Inputs > Element group > Element
Parameter
Function
Present Value
Present input value.
Reliability (Basis
Reliability state for hardware.
Controller)
Interrupt.
Value outside measuring range on 0-10V
DC inputs.
Short circuit.
Calibration lacking. Controller must be re-
turned to the factory.
Internal fault.
Input not configured.
Reliability (Extension
Reliability state for hardware.
Modul POL 955)
Value outside measuring range on 0-10V
DC inputs.
Interrupt for passive sensors.
Short circuit for passive sensors.
Calibration lacking. Controller must be re-
turned to the factory; internal fault or input
not configured.
High limit active
Display an Off normal Alarms, when Pre-
sent Value > High limit.
High limit active
Display an Off normal Alarms, when Pre-
sent Value < Low limit.
High limit
Limit value for a high-limit alarm.
Low limit
Limit value for a low-limit alarm.
Sensor correction
Sensor correction value.
PT1 filter HW
Time constant for the input filter.
Time delay
Alarm time delays for off normal alarms.
Special settings
Go to special settings page.
Special infos
Go to special info page.
Siemens
Building Technologies
18.4.3 Priority array
18.5

Detail pages: Analog inputs

18.5.1 General
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
Time scheduler
Value range
Unit
Off
Stage1
Stage2
Stage3
NULL
Off
Stage1
Stage2
Stage3
NULL
...
Off
Stage1
Stage2
Stage3
NULL
Value range
Unit
Depends on hardware.
OK.
No sensor
Over range
Shorted loop
Other
Process Error
Config Error
OK.
Over range
Under range
Other
Passive
Active
Passive
Active
Depends on hardware.
Depends on hardware.
Depends on hardware.
0...32767
[s]
0...65535
[s]
Standard R S Link
6
X
6
X
Section:
6.4.3
6
X
Standard R S Link
6
4
6
4
6
4
Section:
6.5.1
6
4
6
4
6
4
6
4
6
4
6
4
6
4
4
4