Analog Inputs - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Parameter
Prio 02
Prio 03
Prio 04
Prio 05
Prio 06
Prio 07
Prio 08
Prio 09
Prio 10 bis Prio 14
Priority 15
Priority 16
Access
Example
Parameter
Parameter
Present Value
Reliability (Basis
Controller)
Reliability (Extension
Modul POL 955)
102 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 102
BDCX.100820.01GB
Building Technologies
Range
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Fix Off
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
Off / Stage1 / Stage2 / Stage3 / NULL
The lowest active priority controls the output.
6.5

Analog inputs

6.5.1
General
The details page for analog inputs can be reached multiple ways, including:
• Main Index > Unit > Inputs > Element Group > Plant Element
or
• Main Overview > Plant Element
• Main Index > Unit > Inputs > Temperatures > Outside air
or
• Main Overview > Outside air temp
Range
Depends on hardware.
– OK.
– No sensor
– Over range
– Shorted loop
– Other
– Process Error
– Config Error
– OK.
– Over range
Standard application AHU
Detail pages: Inputs and outputs
Function
ler start up.
Value for priority 2: Not used.
Value for priority 3: Not used.
Value for priority 4 (always Off): Shut off for
error.
Value for priority 5: Forced to a certain value,
e.g. for frost protection.
Value for priority 6: For example, the mini-
mum runtime for the element or overshoot
time, e.g. dampers remain open until the fan
is off.
Value for priority 7: Not used.
Value for priority 8: Manual intervention via
HMI.
Value for priority 9: Special function to reset
from priority 8 to auto mode.
Value for priority 10 through 14: Not used.
Value for priority 15: Normal plant operation.
Value for priority 16: Timeswitch catalogs.
Function
Present input value.
Reliability state for hardware.
– Interrupt for sensors NI1000, PT1000, R2500,
NTC10k,NTC100k.
– Value outside measuring range on 0-10V DC in-
puts.
– Shirt circuit at sensors NI1000, PT1000, R2500,
NTC10k,NTC100k.
– Calibration lacking. Controller must be returned to
the factory.
– Internal fault.
– Input not configured.
Reliability state for hardware.
– Value outside measuring range on 0-10V DC in-
puts. Interrupt for sensors NI1000, PT1000,
CE1P3977en_02
01.02.2010