Modem / Sms - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Remote service inter-
face
Install and commission
Requirements
Commission controller
Note
Siemens
Building Technologies
3)
Wait until:
Main Index > System overview > Save / restore > Config save SD done =
Yes.
– Insert card into the next controller.
– Download data from SD card:
Main Index > System overview > Save / restore > Config save SD = Execute.
– Wait until:
Main Index > System overview > Save / restore > Config load SD done = Yes.
– Reset controller:
Main Index > System overview > Save / restore > Reset required !! = Execute
14.2

Modem / SMS

All Climatix 6XX controller possess a modem interface for an external modem. This
allows for remote service via Saphir Scope. The controller can send alarm SMS. A
Siemens TC35 terminal (GSM modem) required, though. Other GSM modems may
be connected, but are not tested.
14.2.1 Commission Modem/SMS function
Connector type
RJ45 jack, 8 pins.
The connection is located on the upper right-hand side of the controller cover:
P3 9 0 3 Z4 6
The illustration displays pin assignment.
The following steps required to connect a modem:
To the Climatix controller:
Step Action
1
Switch power off
2
Connect modem
3
Switch power on
4
Verify the modem settings
Requirement for commissioning the modem:
• The SAPRO application is fully commissioned.
• Level 4 (password 2000).
• Mapping file (OBH.bin) is loaded.
Step
Action
1
In the menu System parameter > Communica-
tion, select SMS.
2
Configure settings.
You can access the controller after you successfully commission the modem using
the Saphir Scope.
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
SD card and modem
149 / 244
CE1P3977en_02
Page 149
01.02.2010