Main Index > Configuration > Configuration 1 --- Functions
Parameter
Function
Heat recovery
Choose the Heat recovery Unit
Heating
Water Heating
Yes = Heating enabled
PreHeat = Heating + Preheating function
from the Heatingregister
Electrical heating
Choose the Electrical heating Coil
Only one analog Output is enabled
1 step = 1 digital Output
2 step = 2 digital Outputs
3 step = 2 digital Outputs
Cooling
Cooling
If a Dx Cooler is choosed, the analog Output
has to be disabled seperately in IO Config if
not needed
Humidity control
Humidity control
Only Humidification
Only Dehumidification
Humidification and Dehumidification
Heating 2
Additionally Water Heating
Yes = Heating enabled
PreHeat = Heating + Preheating function
from the Heatingregister
El Heating 2
Choose the additionally Electrical heating
Coil
Only one analog Output is enabled
1 step = 1 digital Output
2 step = 2 digital Outputs
3 step = 2 digital Outputs
Cooling 2
Additionally Cooling
If a Dx Cooler is choosed, the analog Output
has to be disabled seperately in IO Config if
not needed
Fire damper
Fire damper
Follow Unit= If Unit switch Off Damper close
Configuration 1
If Configuration 1 is done this must be setted
to done for internal lockings
Reset required !!
After Configuration 1 is setted to done, a
reset is needed before entering
Commisioning 2
Main Index > Configuration > Configuration 2
Parameter
Function
Night cooling
Activate the Night cooling function
Tmp start
Enables Unit start in Unoccupied Mode
according to Temperatur Difference between
the Room and a separate Setpoint
In case of a Htg demand
In case of a Clg demand
In case of a Htg or Clg demand
Boost
Enables Unit start in Unoccupied Mode
according to the next start command from
sheduler
In case of a Htg demand
In case of a Clg demand
In case of a Htg or Clg demand
Tmp start/OSSTP blk Block in Case of Tmp start or Boost
The Damper (bypass Damper is needed)
The Exhaust fan and Damper (bypass
Damper is needed)
180 / 244
Basis Document Siemens Climatix Control System
Siemens
Page 180
BDCX.100820.01GB
Building Technologies
17.7

Configuration 2

Standard application AHU
HMI
Value range
Unit
No
Wheel
PlateExch
Water
No
Yes
Yes+PreHeat
No
Analog
1step
2step
3step
No
Water
Dx 1Step
Dx 2Steps
Dx 3Steps
No
Hum
DeHum
Hum+DeHum
No
Yes
Yes+PreHeat
No
Analog
1step
2step
3step
No
Water
Dx 1Step
Dx 2Steps
Dx 3Steps
No
Yes
FollowUnit
Done
NotDone
Passive
Active
Value range
Unit
No
Yes
No
Htg
Clg
Htg+Clg
No
Htg
Clg
Htg+Clg
No
Damper
Damper+Fan
Standard
R
S Link
Wheel
4
Yes
4
No
4
No
4
No
4
No
4
No
4
Section:
No
4
No
4
NotDone
4
Passive
4
Standard
R
S Link
No
4
No
4
No
4
No
4
Section:
15.2
CE1P3977en_02
01.02.2010
0