17.10 Global Functions; 17.11 Inputs - Siemens Climatix Series Basis Document

Hide thumbs Also See for Climatix Series:
Table of Contents

Advertisement

Main Index > Unit > Global Function
Parameter
Function
Su/Wi calculation
Status of Summer Winter compensation
Manual mode
Status from the Plant if anything is in
Manual Mode
Enable manual alarm Enable the Alarm for Manual Mode
Enable comm test
Enable the comminication Test
Communication test
Staus from the communication Test
Main Index > Unit > Global Function > Su-Wi compensation
Parameter
Function
State
State of Summer Winter Compensation
Su/Wi input
Status of the Heardware input
Outs air tmp damped Actual damped Outside Temperature
Summer date / time
Date and Time for switch over to Summer
Winter date / time
Date and Time for switch over to Winter
Time constant
Time constant for damped Outside
Temperature
Outs air tmp summer If the damped Outside Temperaure > the
this Value => Summer
Outs air tmp winter
If the damped Outside Temperaure < the
this Value => Winter
Main Index > Unit > Inputs > Temperatures
Parameter
Function
Room
Room temperature 1
Room 2
Room temperature 2
Exhaust air
Exhaust air temperature
Supply air
Supply air temperature
Outside air
Outside air temperature
Extract air
Extract air temperature
Hrec supply air
Heat recovery supply air temperature
Heat recovery water
Heat recovery water temperaure
Heating frost
Heating frost protect temperature
Heating 2 frost
Heating 2 frost temperature
Supply air 2
Supply air 2 temperature (needed if Extra
Htg and/or Extra Clg have own sequence
Auxiliary
Auxiliary Temperature
Main Index > Unit > Inputs > Pressures/Flows
Parameter
Function
Supply pressure
Supply pressure
Supply air flow
Supply air flow
Return pressure
Return pressure
Siemens
Building Technologies

17.10 Global functions

17.10.1 General
17.10.2 Su-Wi compensation

17.11 Inputs

17.11.1 Temperatures
17.11.2 Pressures/Flows
Basis Document Siemens Climatix Control System
Standard application AHU
BDCX.100820.01GB
HMI
Value range
Unit
Winter
Summer
Manual
Auto
No
Yes
No
Yes
Off
On
Value range
Unit
Winter
Summer
Winter
Summer
0...36000
h
-64...64
°C
-64...64
°C
Value range
Unit
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
-64...64
°C
Value range
Unit
0...5000
Pa
0...40000
l/s
0...5000
Pa
Standard
R S Link
X
X
No
6
Section:
5.1.1
No
6
Off
Standard
R S Link
Section:
5.1.2
24.0
6
16.0
6
14
6
Standard
R S Link
x
x
x
x
x
x
Section:
x
15.3.2
x
x
x
x
x
Standard
R S Link
x
x
Section:
x
15.3.3
189 / 244
CE1P3977en_02
Page 189
01.02.2010

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Oem seriesPol955Pol638 series

Table of Contents