Exception Codes For Beam Sensor - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Exception codes for Beam sensor

Gen
Pos
type
No.
Description
1st
Subfire
background
E
N
V
2nd
Subfire
I
foreground
O
R
N
M
3rd
E
N
T
4th
Total beam
obscuration
5th
Drift out of
range high
S
6th
Drift out of
E
range low
N
S
O
R
7th
Noisy (High
frequency)
8th
D
9th
device
E
firmware
V
I
C
E
10th
device
transmission
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Exception codes
normal band sub fault band
0
1
None
Small signal
sensed [Check
location, state
& type]
None
Small signal
sensed [Check
location, state
& type]
OK
OK
OK
OK
Single HF fall
seen
OK
Isolated fault
[Note/report]
OK
Low error rate
Vigilon (EN & BS) Compact (VA) panels
2
Subfire
[Check location,
state & type]
Subfire
[Check location,
state & type]
Out of
Specification.
[Clean/check
gain/
repair]
Multiple HF fall
seen
Repetitive fault
[Note/report/
replace]
Medium error
rate
[Report]
fault band
3
Obscured for
>1 minute or
Tx failed
[Replace]
Gain not set
correctly
[Check gain
/replace]
Below lower
limit
[Clean/check
gain/replace]
Total failure
[Replace]