Generic Commissioning instructions
Heat Sounder (S4-780)
Dual Optical Heat
Sensor Speech strobe
(S4-711-ST-VO & S4-771)
Dual Optical Heat CO Sensor
Speech & Strobe
(S4-911-ST-VO)
All S4 range of sensor sounder devices meet CEA GEI 1 - 084 Requirements and test methods for input/output devices for use on
the transmission paths of fire detection and alarm system.
~ Meets following tone settings High tone ( Continuous 933Hz) & Alternate (High 933Hz for 0.25s / low 700Hz for 0.25s)
On initial power-up the system selects state 0 for all devices.

34xxx Sensors

The following 34xxx sensors when operating in the state shown below are LPCB approved to the respective standard.
Product number Description
Compact "O"
Optical sensor
34710
Optical heat sensor
34720
Heat sensor
34770
Optical heat sounder sensor EN 54 : Part 5, part 7 and LPCB requirements #
34800-EN
Manual Call Point
34842-EN
Manual Call Point
¨
If a 34xxx sensor is configured to operate a non LPCB approved state, then this will contravene the LPCB approval.
* - these devices are LPCB approved when operating in the LPCB approved STATE, see table below.
"
All the LPCB states applicable to fire sensors are shown below. The required state is configured during
commissioning and can be configured at the control panel.
Device
Optical heat sensor
(34770 and 34710)
Heat sensor (34720)
Heat sounder
(34780)
On initial power-up the system selects state 0 for all devices.

Sounder Strobe

The following S-cubed Mark 1 range of products are LPCB approved to EN 54 : Part 3
S3-SN-R, S3-SN-W, S3IP-SN-W, S2IP-SN-R, S2IP-SN-W, S2IP-SN-R3, S2IP-SN-W3, S3-SN-ST-RR, S3-SN-ST-WR,
S3IP-SN-ST-RR, S3IP-SN-ST-WR, S3IP-SN-ST-RW and S3IP-SN-ST-WA.

Interface Units

The following products are approved to prEN 54 Part 18 : 2005
34410
Zone module (loop powered)
34450
4 Channel Input / Output Interface unit (loop powered)
34415
Single channel Interface unit
10
Device
LPCB approved
sensor STATE *
State 0
State 5
State 0
State 5
State 8
State 0
State 9
Approval
EN 54 : Part 7 #
EN 54 : Part 5 and Part 7 #
EN 54 : Part 5 #
EN54 Part 11
EN54 Part 11
LPCB approved sensor
STATE #
State 0
State 8
State 12
State 13
State 0
State 1
State 0
State 12
Meets
Class A1 heat
Class B heat
Medium optical smoke / Class A1 heat
Medium optical smoke / Class B heat
Delayed medium optical smoke / Class A1 heat
Medium optical smoke / Class A1 heat
Class A1 heat
Meets
Medium smoke sensitivity with Grade 2 heat
Smoke sensing with delay + Grade 2 heat
Grade 1 heat only
Grade 2 heat only
Default sensitivity
Grade 1
Grade 2 heat
Grade 1 heat