Mains supply
Dedicated mains supply
from consumer unit
5A Unswitched fused
spur unit
PANEL
FS3 3.15A(T)
Mains fuse
&
Ensure that the mains supply cable enters
the panel through a dedicated cable entry point.
"
These fire alarm system products are NOT
designed to be powered from IT Power systems.
All mains powered equipment must be earthed. Mains supply to
any fire alarm control and indicating equipment must be via a
dedicated unswitched 5A fused spur unit, which should be clearly
labelled FIRE ALARM - DO NOT SWITCH OFF.
A disconnect device must be provided to disconnect both poles
and must have a minimum gap of 3mm. The Disconnect device
should be available as part of the building installation and must
be easily accessible after installation is complete.
&
Hazardous voltage remains after operation
of a protection fuse. Take appropriate action to
guard against the risk of equipment having exposed
live mains supply.
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
N E
L
P2
DANGER
Vigilon (EN & BS) Compact (VA) panels
PSU Indicators
P3
43V
FS6
1A P7
BAT1
-
+
Y1 Y2 G1
Description
Y1
(yellow)
Normal condition
(no faults in the
system)
Mains out of limit
24VDC failure only
Battery 1 failure only
Battery 1 and
24VDC failure
43VDC failure only
fast flash
No power to PSU
Earth fault only
On
Note on initial power up all three LEDs on the PSU will
switch on for approximately 1 second duration.
PSU BOARD
Y1 Y2 G1
Y2
G1
(yellow)
(green)
fast flash
slow flash
fast flash
fast flash
slow flash
fast flash
slow flash
fast flash
fast flash
On
On
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gent viglion compact voice alarmGent viglion compactGent viglion bs

Table of Contents