Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 103

For the fire alarm systems
Table of Contents

Advertisement

Message
Device power
too high/
restored too low
/restored
number x on
loop y
Device Replaced
is faulty
number x on
Loop y
Device Replaced
number x loop y
Device soft
address; SAFE:
number x on
loop y
Device Mains
Failed /
Restored number
x loop y
Disables Cleared
Duplicate SAFE
Address error:
number x on
loop y
Earth Fault/
Fault Cleared
Enabled Aux
relay x
Disabled Aux
relay x
End switching
normal at card x
Exception number
x on loop y
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
associated with..
meaning..
Device
Internal power rail of mains
powered interface unit has
a value of rectified DC
equal to or greater than
32V (high) / less than 30V
(restored)
DC equal to or less than
24V (low) / greater than
26V (restored)
Loop Processor
Tx fault re-finding device.
Card
Loop Processor
The replaced device is now
Card
communicating with the
panel.
Device
Device primary address
does not match SAFE
address.
Device
Failure of mains supply to
mimic/repeat /mains
powered interface unit. The
value of rectified DC is
equal to or less than 8V i.e.
failed.
MCC / MCB (main
All disablements have been
control card/board)
removed from the panel.
Device
Two devices on a loop
have the same SAFE
address.
Power supply
The ADC value to earth of
the 8V regulator is equal to
or greater than 5 (for a +ve
fault)
or less than 3 ( for a -ve
fault).
MCC / MCB (main
The auxiliary relay has
control card/board)
been enabled or disabled
automatically or manually.
Network
Network card is back to
normal operation, (see also
end switching disabled)
(Exceptions also
Condition pattern has been
referred to as
matched.
Sub-Fault)
Loop Processor Card
Vigilon (EN & BS) Compact (VA) panels
..possible action
Replace the device
Check connections to device /
base and also device type etc.
-
Check loop configuration.
Check mains supply
connections and the mains
fuse. When the rectified DC
is greater than 24V it is
restored.
-
Change one of the SAFE
address.
A clear indication is normally
given when ADC is equal to
64.
If necessary, manually
enable/disable the auxiliary
relays using the [control]
menu.
-
Check the condition codes.
103