Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 183

For the fire alarm systems
Table of Contents

Advertisement

VIG-MIM-A4 A4 Mimic panel
Local buzzer
disable
Figure 3-4
Mimic display to
Control unit
connections
cdm19
Vigilon Sys tem Com mis sioning
NOTE: If slight repositioning is required, the low-tack adhesive sheet
allows the plan sheet to be removed and replaced as required.
f)
If required, insert a link to short pins P3 on the mimic display PCB to
disable the local buzzer.
NOTE: With the buzzer disabled there will be no local buzzer indication
in the event of a fire or fault condition.
g)
Refit the LED housing to the door frame using screws previously
removed.
h)
Ensure the cable connections from the Mimic control unit are made at
the Mimic display unit.
NOTE: Ensure the cable screen is earthed to both the control unit and
display unit.
i)
Close and lock the door.
A4 Mimic Con trol unit
This unit requires a custom EPROM to be fitted to the master repeat card,
in the mimic control unit, see also the Mimic configurer part of this manual.
q Open the mimic control unit door.
q Make the cable connections between the A4 Mimic display unit and
the mimic control unit. Connect also the loop and mains supply cables.
q Check all internal connections are secure.