Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 173

For the fire alarm systems
Table of Contents

Advertisement

VIG-INT-1CH Single channel interface
Rotary switch
Configurations
Input/Output
line test
Line module
switch
Vigilon Sys tem Com mis sioning
q Set the rotary switch SW1 (on the interface board) for the required
input.
Rotary
Switch
(SW1)
position
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
N/O = Normally open
NOTE: An input circuit is monitored for both open or short circuit fault.
The single channel interface unit can be configured to operate:
q Single input
q or Multiple input
q with Output signal via relay change over contacts
At an appropriate stage of commissioning the interface input and output
circuits must be tested as per project specification. The tests are based on
the type of equipment interfaced.
Sin gle in put
NOTE: When the single channel interface unit is configured to accept
single input then a line module must be used.
q The line module may be installed in a remote location up to 100m cable
distance away. Its two position switch must be set to input.
In ter face and panel out sta tions
Input circuit
mode of input
function.
circuit
To monitor:
operation
Off
Off
Multiple inputs
Fire
Multiple inputs
Fire
Single input
Fire
Single input
Fire
Single input
Fire
Single input
Fire
Single input
Fault
Single input
Fault
Single input
Fault
Single input
Fault
Single input
Supervisory
Single input
Supervisory
Single input
Supervisory
Single input
Supervisory
N/C = Normally closed
normal
delay
status of
(seconds)
the input
before
signal
signal is
accepted
N/O
0s
N/O
30s
N/O
0s
N/O
30s
N/C
0s
N/C
30s
N/O
0s
N/O
30s
N/C
0s
N/C
30s
N/O
0s
N/O
30s
N/C
0s
N/C
30s