Device Checks; Checking The Time Averages - Honeywell Gent Viglion EN54 Generic Commissioning Instructions

For the fire alarm systems
Table of Contents

Advertisement

Device checks

"
Ensure all dust covers have been removed from the sensor heads and the system is allowed to operate for at
least 24 hours to obtain accurate time average and condition code readings.

Checking the time averages

You can manually recover card data. The following
procedure assumes there is no password access
required. Press the Menu On/Off button and then
[Info], momentarily press <etc> to select [Time
Avg] and type in the channel number from the
range 1-6, select [Device] and type in the device
number for which the time average is required,
select [Loop] and type in the loop number of the
device ->[Enter]. The display shows time averages for the device.
Foreground (fast) time average readings
Tnew
T1
T2
On
80mS 320mS 1.28S 5.12S 20.48S 1.36min 5.46min 21.84min 1.45hr 5.82hr 23.3hr
demand
Normally reads 252, unless there is a
threshold.
Device type 34K
Optical
Heat
Heat
Beam Transmit
Beam Receive
Device type S-Quad
Heat Sensor
Heat Sensor Sounder
Dual Optical Heat Sensor
Dual Optical Heat Sensor Strobe
Dual Optical Heat Sensor Sounder
Dual Optical Heat Sensor Speech Strobe
Dual Optical Heat Sensor CO
Dual Optical Heat Sensor CO Speech Strobe
4188-856_i2_12/06_Generic Vigilon (Compact + VA) Comms.
Tnew (On demand)
Foreground (fast) Time
average readings T1 to T5 of
Channel 1 Device 1 loop 1
Background (slow) Time
average readings T6 of T11
Channel 1 Device 1 loop 1
T3
T4
T5
Analogue Channel
Time average
number
Tnew
1
200 - 235
2
180 - 210
180 - 210
0
2
150 - 170
Analogue Channels
2 - heat
2 - heat
1 - optical (forward)
2 - heat
4 - optical (backward)
1 - optical (forward)
2 - heat
4 - optical (backward)
1 - optical (forward)
2 - heat
4 - optical (backward)
1 - optical (forward)
2 - heat
4 - optical (backward)
1 - optical (forward)
2 - heat
3 - CO
4 - optical (backward)
1 - optical (forward)
2 - heat
3 - CO
4 - optical (backward)
Vigilon (EN & BS) Compact (VA) panels
Time average readings of Channel 1 device 1 loop 1
Average Channel 1 Device 1 Loop 1
19
252
252
252
e Aver channel 1 Device 1 Loop 1
[Repeat]
[Previous]
Background (slow) time average readings
T6
T7
T8
Time average Tnew
66
66
25
66
40
25
66
40
25
66
40
25
66
40
25
66
25
40
25
66
25
40
23:15
252
252
19 19 19 19 18 18
[Next]
[Cancel]
T9
T10
T11
51