Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 179

For the fire alarm systems
Table of Contents

Advertisement

VIG-RACK Interface rack unit
Figure 3-6 DIL switch
settings for rack
interface board
cd8m086
Vigilon Sys tem Com mis sioning
<——— Switch S1—--><Switch S2->
Channel —>
CH1
Switch No>
1 2 3
1 = On
0 0 0
0 = Off
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
NOTE: The supervisory mode is a non fire input used to trigger a
command build.
Switch S2
5 6 7 8
No—>
0 0 0 0
0 0 0 1
0 0 1 0
0 1 0 0
1 0 0 0
q Partially slide each card into the respective socket. The rack unit can
accommodate up to 10 cards.
NOTE: The interface cards must be installed with ribbon header at the
front for connection to the front line terminal modules.
q Connect each interface card to either the respective line-terminal
module or keyswitch. Then fully slide the interface card into the rack
and ensure it is fully seated into its socket.
NOTE: A keyswitch door option can be fitted to this rack unit. The door
can accommodate up to 28 off 2-way keyswitches or 20 off 3-way
keyswitches, limited by 40 inputs, see keyswitch door option.
Interface and panel outstations
CH2
CH3
CH4
4 5 6
7 8 1
2 3 4
0 0 0
0 0 0
0 0 0
0 0 1
0 0 1
0 0 1
0 1 0
0 1 0
0 1 0
0 1 1
0 1 1
0 1 1
1 0 0
1 0 0
1 0 0
1 0 1
1 0 1
1 0 1
1 1 0
1 1 0
1 1 0
1 1 1
1 1 1
1 1 1
Channel No
All
CH1
CH2
CH3
CH4
Mode
Fire (normally open)
Fault (normally open)
Supervisory (normally open)
Not in use (channel not set up)
Fire (normally closed)
Fault (normally closed)
Supervisory (normally closed)
Output
Delay
No delay
10 seconds
10 seconds
10 seconds
10 seconds