Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 184

For the fire alarm systems
Table of Contents

Advertisement

In ter face and panel out sta tions
VIG-MIM-A4 A4 Mimic panel
Figure 3-5 Components and battery connection
cdm21
Local buzzer
q If required, insert a link to short pins P1 on the master repeat card PCB
disable
to disable the local buzzer.
NOTE: Under mains fail condition, that is with only the green power and
yellow fault LEDs On, the optional battery if installed will provide a
standby supply to the unit for up to 72 hours plus 0.5 hour alarm load.
NOTE: If the local buzzer is enabled, then there is no means of locally
cancelling the buzzer during local fault condition. The buzzer is
automatically cancelled when the main panel buzzer is cancelled.
Vigilon Sys tem Com mis sioning

Advertisement

Table of Contents
loading