Honeywell Gent Viglion EN54 Generic Commissioning Instructions page 148

For the fire alarm systems
Table of Contents

Advertisement

Installation instructions
IO card location
One new IO card is normally fitted as Card 15 in socket P2 of
the Control panel backplane.
P1
To DKC
P4
LCC - P1
IOC- P2
LOOP 1 - P3
LOOP 2 - P4
LOOP 3 - P5
LOOP 4 - P6
P7
P8
Backplane
Setting switches SW1 and SW2
On
Off
SW1
new IO Card
1 2 3
P3
"
IMPORTANT:
The Vigilon Control Panel make use of the DIP switches
on the DKC, located on the inner door. The switches are
used to set address and baud rate. It is important that the
DIP switches SW1 on the IO card are ALL set in the UP or
OFF position so that they are ignored.
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK.
by Honeywell
Telephone +44 (0) 116 246 2000
2
SW1 Switch settings
The switch positions shown here are applicable for the new IO
Card when installed as an additional IO card.
"
40 way ribbon
cable
work when used as second or additional IO card.
20 way ribbon
cable
Local Controller card
Input/Output card
1
Loop Processor card
Off Off Off 1200 baud
Space for 3 Loop
Off Off On 1800 baud
Processors
Off On Off 2400 baud
Off On On 3600 baud
Network card
On Off Off 4800 baud
On Off On 7200 baud
On On Off 9600 baud
On On On 19200 baud Off Off On On On
SW2 Switch settings
Rotary
Switch
Pos.
P2
SW2
Factory
set to 5
IC4
new IO Card EN54 (VIG-IOC-DOM)
No dongle is required for DIP switches to
Baud Rate
2
3
|
4
Off Off Off Off Off
Off Off Off Off On
Off Off Off On Off
Off Off Off On On
Off Off On Off Off
Off Off On Off On
Off Off On On Off
On On On On On up
Factory settings
Standard connections
Port 0 (RS232) Mode
0
3217 Half/Full-Duplex
1
Slave I/O
2
Remote Printer (as
VIG-IOC-PRT)
3
Universal Full-Duplex (as
VIG-IOC-UFD)
4
Ascom Pager (as
VIG-IOC-ASCOM)
5
Domain Bridge Full-Duplex
6
Universal Half-Duplex (as
VIG-IOC-UNI)
7
-
Factory setting
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
new IO Card (EN54) 4188-777 issue 3_11/05
Node Address
5|
6
7
8
|
1
2
3
4
5
6
7
|
to
31
Port 1
(RS485 mode
Switch
position from
0 to 7 sets this
port for
Repeat panel
at 1200 baud.
Switch
position from
8 to F sets
this port for
other
applications
at 9600 baud.
Website: www.gent.co.uk