Report Style; Event Codes - Honeywell NOTIFIER NFW-50X Manual

Addressable fire alarm control panel
Hide thumbs Also See for NOTIFIER NFW-50X:
Table of Contents

Advertisement

Master Programming Level
To set the Trouble Report Limit, press 3 while viewing Communicator Screen #1. The following screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Report Limit to this value. Refer to the table on page 46 for permissible set-
tings.
NOTE: Entering a value of 00 will disable the Trouble Report Limit allowing the Communicator to call the Central Station an unlimited
number of times.

Report Style

COMMUNICATOR
1=REPORT STYLE

2=EVENT CODES

Communicator Screen #3
NOTE:
1. Detector/Module Address 001 will be reported to the Central Station as Point 001.
2. Detector/Module Address 002 will be reported to the Central Station as Point 002 with reports continuing in a similar fashion up to
Detector/Module Address 50 which will be reported as Point 50.
Event Codes
COMMUNICATOR
1=REPORT STYLE
2=EVENT CODES
Communicator Screen #3
Select the desired communication format to update Event Code programming.
Pressing the down arrow key allows viewing of all Events associated with the selected Communication Format. Pressing the number cor-
responding to the event displayed in each screen will display its default event code which can be customized by the programmer. For
example, pressing 1 for Pull Station will display the following screen which allows the Event Code to be changed from the default value.
The tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats.
The information shown in Table 3.3 is automatically programmed for the Central Station phone number Event Codes when the Ademco
Contact ID or SIA Format is selected. Enter 0s for an Event Code Setting to disable the report. Disabled reports will not get called to the
Central Station. The programmer may enable the Event Types in programming as described on the previous page.
Event Description
PULL STATION
MON-USER-DEF-1
WATERFLOW
MON-USER-DEF-2
SMOKE (PHOTO)
DET-USER-DEF-1
SMOKE (ION)
NFW-50X Manual — P/N LS10129-001NF-E:C 7/25/2018
Pressing 1 while viewing Communicator Screen #3 will cause the Report Style display to toggle between
POINT
Point and Zone. Setting the Report Style to Point will program the Communicator to report individual point
status to the Central Station. The control panel is capable of monitoring a total of 50 addressable devices.
Setting the Report Style to Zone will program the Communicator to report zone status to the Central Sta-
tion. The control panel is capable of monitoring a total of 20 individual zones.
Pressing 2 while viewing the Communicator Screen #3 will cause the following screen to be displayed:
POINT
1=ADEMCO CONTACT ID
2=SIA8
3=SIA20
Active
115
115
113
113
111
111
111
TROUBLE CALL LIMIT
RANGE 00-99

Trouble Report Limit Screen
EVENT CODES
Event Code Screen
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
PULL STATION
ALARM
000
Event Code Screen
Ademco Contact ID
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Table 3.3 Event Codes
Programming
SIA
Active
Restoral
FA
FH
FA
FH
SA
SH
SA
SH
FA
FH
FA
FH
FA
FH
83

Advertisement

Table of Contents
loading

Table of Contents